(4) 1/2 split-range version
The I/O specifications for the 1/2 split range version are listed below.
Adjust the zero and span settings using the same procedure as for the standard range
version.
Range
4~12mA
12~20mA
4-3

Width of Range Adjustment

The table below shows the width of the zero and span adjustment bands.
You can set the range to be different to the standard 0 to 100% output provided you stay
within these limits.
Zero adjustment width
Span adjustment width
0%
100%
4mA
12mA
12mA
20mA
-10%~+10%
+75%~+125%
4-3