Free2Move eSolutions eProWallbox Series Konfigurationshandbuch - Seite 11
Blättern Sie online oder laden Sie pdf Konfigurationshandbuch für Zubehör für Kraftfahrzeuge Free2Move eSolutions eProWallbox Series herunter. Free2Move eSolutions eProWallbox Series 16 Seiten. Modbus rtu
CURRENT_LIMIT: 40407
The address contains the current limitation value that can be set remotely through third-party
EMS in real time.
NOTE: The lower current limit value set (e.g. the one set on the Rotary Switch) will always pre-
vail. The minimum current limit value to be set is 6A.
FALLBACK_CURRENT: 40409
With this register is possible to set the fallback current in case communication with third-party
EMS is lost.
The default value is set to 32000 mA.
METER_USED: 40411
With this register is possible to indicate if another meter, external from the charging station, is
installed:
•
0 = External Meter
•
1 = Internal Meter
WATCHDOG_TIMER_ENABLED: 40412
With this register is possible to enable the load unbalance and fallback current functions:
•
0 = Watchdog timer disabled; functions disabled
•
1 = Watchdog timer enabled; functions enabled with the following default logic:
•
•
•
WATCHDOG_TIMER: 40413
When the timeout occurs (Address 40412 = 1) the timer will start. If the timer runs out, the fal-
lback current function and the load unbalance function are enabled.
Default value: 600 s.
A 600 s timer will start
If in the 600 s the reset signal (Address 40502) is sent, the charging station
doesn't react
If the timer runs out, the fallback current (Address 40409) and load unbalance
(Address 40402) functions will be enabled
MODBUS RTU
C o n f i g u r e a t i o n G u i d e
11