Aplisens SGE-25.SMART Benutzerhandbuch - Seite 11

Blättern Sie online oder laden Sie pdf Benutzerhandbuch für Zubehör Aplisens SGE-25.SMART herunter. Aplisens SGE-25.SMART 20 Seiten. Smart level probes
Auch für Aplisens SGE-25.SMART: Benutzerhandbuch (20 seiten)

Aplisens SGE-25.SMART Benutzerhandbuch
6.

INSTALLATION

6.1. General recommendation

Smart level probes are installed where liquid levels are measured in wells, tanks, boreholes, etc. The
probe is immersed in the measured medium. The probe is immersed in the measured medium. A special
cable extends above the medium level, which can be connected directly to the probe device or to a
junction box. The probe may be hung on the supply cable using Aplisens SG cable hanger (item 1 on
Fig. 2). In case of frequent removal of the probe or when there is a risk of catching on protruding
elements during pulling up, it is recommended to hang the probe on a steel cable using the carrying
eye (item 2 on Fig. 2).
Figure 2. Mounting brackets for probes.
If there is a possibility of turbulence, the probe should be installed in a casing pipe (e.g. PVC).
Do not clean or touch the diaphragm with hard or sharp objects. Hang the probe with the additional
Teflon shielding on the cable on the suspension cable or on the inner cable (do not grab the Teflon
shield).
Immediately before inserting the probe into the medium to be measured, remove the
protective cover from the front membrane (not applicable SGE-25.Smart).
During installation protect the probe from mechanical impacts.
Figure 3. Diaphragm cover for SGE-25C.Smart and SGE-25S.Smart probes.
Revision 01.A.001/2021.09
EN.IO.SGE.25.SMART
11