__________________________________________________Battery Charger
Rail mounting:
Other modules must have a minimum vertical distance of 10 cm to this power supply in order to guarantee sufficient auto
convection.
Use and Connections
Caution:
Switch off the system before connecting the module. Never work on the machine when it is live.
Charging Level Current: With trimmer from 20% to 100% of In. Select the max. battery charge current estimated from 10 to 25% of
the nominal capacity.
- Connection to Battery module (Output 1) 3-4 Pin: Battery Input and diagnosis led: very fast blinking= recovery charging ( when
the battery is too low) , fast blinking=fast charge, slow blinking=trickle charge
- Connection to Out Load (Output 2) 1-2 Pin: Output voltage 24 Vdc is made via the +, - .
- Monitor Mains or Backup: Mains with led off and closed contact (5-6), Backup with led on and closed contact (5-7).
Note: switching of the relay Backup should be filtered with a delay of at least 5 seconds, example: connection to PLC.
- Monitor Low Battery or Battery replacement: Normal condition with battery OK, led Off and closed contact (8-9), Low Battery with
battery NOK, led ON and closed contact (8-10), Battery replacement alarm with Power ON , led ON and closed contact (8-10); (see
diagnostic Led )
Life Test Battery : In trickle charge condition check every 4 hours, internal impedance (Battery non Ok 5 blinking Diagnosis Led)
Diagnosis Led
Very fast blinking= recovery charging ( when the battery is too low, Under 10 Vdc)
Fast blinking= fast charge.
Slow blinking= trickle charge (floating charge)
1 blinking= Reverse polarity battery; Bad input voltage battery.
2 blinking= Battery not connected.
3 blinking= Short circuit battery element.
4 blinking= Over Load.
5 blinking= Bad battery.( Internal impedance Bad or Bad battery wire connection)
Cable connection
The following cable cross-sections may be used:
2
At the Input: 0.2÷2.5 mm
rigid / flexible
2
At the Output: 0.2÷2.5 mm
Strip the connection ends: 7mm
Input: The input connection is made by the screw connections L, N, PE
NB: (BRIDGE ONLY for 115 Vac) only for 115 Vac supply
INSTRUCTION MANUAL
Assembly: pull down the plastic block with
a screwdriver, place the CB on the rail and
release the plastic block.
The CB is now assembled on the rail.
rigid / flexible
All specification are subject to change without notice
Disassembly: pull down the plastic block and pullout
the module like the arrow in the scheme
.
2