7.2 SELECT OUTPUT VOLTAGE (ONLY SIZE4 CBI280)
No.17: Caution: Switch off the system before Setting the Jumper. The Jumper is Read at the device
power-up only.
Output Voltage Selection
Output Voltage Selection
8 DRIVE AND MONITORING
8.1 FAULT - STATUS CONDITIONS (ISOLATED RELAY):
8.1.1 STATUS: Mains or Backup: Input Mains On/Off.
• No.5 Relay Contact: 5, 6, 7
• No.6: Led
8.1.2 FAULT: Low Battery, Battery Replacement, Faulty Battery or Faulty System
• No.4 Relay Contact: 8,9,10
• No.8: Led DIAGNOSIS: Battery charger mode, or, Diagnosis of the system through "blinking code"
Light signal
8.1.3 Back Up and Fault: Relay and LED Conditions
Relay:
ON
Mains Input
Vac
OFF
YES
Battery SOC
less than 30%
NO
Battery or
YES
system Fault?
NO
Note:
(1) Contact relay Mains/Back switch at least 5 seconds after disconnection of Power.
(2) See Diagnosis Led
8.1.4 Relay Contact Rating:
Max.DC1: 30 Vdc 1 A; AC1: 60 Vac 1A: Resistive load (EN 60947-4-1).Min.1mA at 5 Vdc: Min.
permissive load
8.1.5 Charging Mode STATUS
Status (Led)
Float
Charging
Absorption
Type
Boost
Recovery
8.1.6 Faulty Battery / Faulty System
Reverse polarity or high battery Voltage
(over 32.5Vdc for CBI 24xxA)
Battery No connected
Element in Short Circuit
Over Load or short circuit on the load
Bad battery; Internal impedance Bad or Bad battery wire
connection
Life test not possible
Boost condition; battery discharge after 4 min. of overload.
Internal fault
Low battery (under 18.5Vdc for CBI 24xxA) Only if started from
battery, no Mains input, from Jumper N°5 or Push Bottom
Master-Slave connection lost between the master and slave on
parallel configuration, (AP device only)
Bad battery wire connection; Parallel mode on Slave Device
Boost condition; battery discharge after 4 min. of overload;
Parallel mode on Slave Device
Port N°5 - Led N°6 Mains/Back-Up
5-6 Closed
5-7 Closed
■ - led off
■ - led On (1)
■ - led On
■ - led On
■ - led off
■ - led off
Jumper
24 Output Voltage
No Jumper
12 Output Voltage
Port N°4 - Led N°7 Fault Battery
8-9 Closed OK
8-10 Closed
■ - led off
■ - led off
■ - led On (2)
■ - led off
■ - led On
■ - led off
Diagnosis (No.8)
1 Blink/2 sec
1 Blink/sec
2 Blink/sec
5 Blink/sec
1 Blink/pause
2 Blink/pause
3 Blink/pause
4 Blink/pause
5 Blink/pause
6 Blink/pause
8 Blink/pause
9 Blink/pause
10 Blink/pause
11 Blink/pause
13 Blink/pause
15 Blink/pause
Fault
Battery
(No.7)
OFF
OFF
OFF
OFF
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON
ON