Specifications
Power 24 VAC ± 10% 50-60 Hz at 350 mA,
8.4 VA supplied by the 14 conductor
ribbon cable (see Figure 2).
Software Requirements Screen files
must be transferred to the module
connected to the BACview
2
BACview
Programmer's Guide and the
BACview Programmer's Tutorial for further
information.
Module Interface 14-pin proprietary
auxiliary device port.
Hardware Requirements Use the
2
BACview
with any Exec 6.0 (or later)
control module with a 14-pin auxiliary
device port. For instructions on using the
2
BACview
, refer to the BACview
Guide.
Operating Temperature Range 32 - 120
°F, or 0 °C to 48.9 °C; 10 to 90% relative
humidity (non-condensing).
Protection Provides 12KV human
discharge model protection to the
encloser.
Listed By PAZX (UL 916), cUL C22.2
No.205-M1983.
Rear Mounting
Plate Screws
Revised 11/19/99 • BACview
2
. Refer to the
2
User's
Mounting Holes
Mounting Holes
Figure 2. Rear Mounting Plate
2
Hardware Guide
3
Mounting
2
The BACview
rear mounting plate (see
Figure 2) has four mounting holes and one
opening for the 14 conductor ribbon cable.
The rear mounting plate can be removed by
releasing the four screws on the sides and is
used as a template for mounting. There are
typically two different types of mounting,
Types I and II.
NOTE If this equipment is used in a manner
not specified by the manufacturer, the
protection provided by the equipment may be
impaired.
Type I Mounting
2
The BACview
can be mounted onto a panel
directly above the module it will
communicate with (see Figure 3 on page 4).
1. Remove the rear mounting plate screws
(see Figure 2 for location) from the
2
BACview
.
2. Remove the rear mounting plate from the
2
BACview
.
14 Conductor
Ribbon Cable
14 Pin TTL Connector