Celec S-50 Handbuch für die Installation vor Ort - Seite 9
Blättern Sie online oder laden Sie pdf Handbuch für die Installation vor Ort für Controller Celec S-50 herunter. Celec S-50 10 Seiten.
Field Installation Manual
Model
Phase Configuration
Maximum Line Voltage
Maximum Power
Steps
Monitoring
Accuracy
Frequency
Protection
Equipment Protection
Circuit breaker Required
Low Losses
Human Protection
Operating temperature range
Dimensions(L X H X D)
Operating Life
Dielectric Strength
Wire Gauge & Rating
Unit Weight
______________________________________________________________________________________
S-50
Electrical Data Sheet
S-50
Three Phase 208V AC WYE/Delta
208V AC
50 kVar
8
PF, kVA, kVar, Volt, Current, KW, %THD-V
Internal Temperature & Capacitor Status
1 kVar
60Hz
Capacitor Inbuilt Protection P2, capacitor short circuit 10,000A
Capacitor over current protection.
Internal design has adequate clearance and creepage distance
against line transients. MOVs not required.
200 Amp 3 pole
1.5 Watt each step
All High voltage shielded from contact.
o
40
C Ambient
( 800 x 1000 x 3000 mm) Metal Enclosure Type 1
Switching tested up to 25,000 times,
Tested up to 3.5 kV, 1.42 kV for 1 min.
3/0 AWG Str for Power, 18-22 AWG Str for CT, 8 AWG Str for Bonding
84 kg (186 Pounds)
9