Automation Direct DURApulse GS4 Schnellstart-Handbuch - Seite 5
Blättern Sie online oder laden Sie pdf Schnellstart-Handbuch für Controller Automation Direct DURApulse GS4 herunter. Automation Direct DURApulse GS4 9 Seiten. Ac drive
DURApulse GS4 AC Drive Quick-Start Guide
Parameter Settings Tables
Multi-Function Input Settings for P3.03~P3.10
15: Operation speed command from AI1
0: no function
16: Operation speed command from AI2
1: Multi-Speed/PID Multi-Setpoint bit 1
17: Operation speed command from AI3
2: Multi-Speed/PID Multi-Setpoint bit 2
18: Forced Ramp Stop by P3.56 (no error)
3: Multi-Speed/PID Multi-Setpoint bit 3
19: Digital Freq Up Command
4: Multi-Speed bit 4
20: Digital Freq Down Command
5: Reset
21: PID function Disable
6: JOG
22: Clear counter
7: Accel/Decel speed inhibit (Speed
23: Increment counter value (DI6 only)
Hold)
24: FWD JOG
8: 1st~4th Accel/Decel time selection,
25: REV JOG
bit 0
26: Emergency Stop EF1 (Coast stop)(EF1
9: 1st~4th Accel/Decel time selection,
error)
bit 1
27: Signal Confirmation for Y-connection
10: External Fault Input by P3.56 (EF error)
28: Signal Confirmation for Delta
11: Base Block Input
connection
12: Drive Output OFF
29: Disable EEPROM Write
13: Disable Auto Accel/Decel Time
30: Forced Coast Stop
14: Switch between drive settings 1 and 2
31: Hand Contact for HOA Control
32: Auto Contact for HOA Control
Multi-Function Output Settings for P3.17~P3.20
0: no function
20: Warning Output
1: AC Drive Running
21: Over Voltage Alarm
2: At Frequency Setpoint
22: Oc Stall Alarm
3: At Speed 1 (P3.32)
23: Ov Stall Alarm
4: At Speed 2 (P3.34)
24: External Control Mode
5: At Zero Speed Including Drive Running
25: Forward Command
6: At Zero Speed Drive not Running
26: Reverse Command
7: Over Torque Level 1
27: Above Current Output (≥ P3.52)
8: Over Torque Level 2
28: Below Current Output (< P3.52)
9: Drive Ready
29: Wye Connected Command
10: Low Voltage warning (Lv)
30: Delta Connected Command
11: Error indication (All faults, Except for
31: Zero Speed at Drive Running
Lv Stop)
32: Zero Speed including Drive Stop
12: Brake Release Function (P3.51)
33: Fault Option 1 (P11.00)
13: Over-temp Warning
34: Fault Option 2 (P11.01)
14: Dynamic Braking Output
35: Fault Option 3 (P11.02)
15: PID deviation error
36: Fault Option 4 (P11.03)
16: Over Slip (oSL)
37: At Speed (Setpoint include 0Hz)
17: Middle Count Value Attained (P3.45)
38: Brake Function
18: Final Count Value Attained (P3.44)
39: Under Ampere (Low Current)
19: Base Block Indication
Analog Input Settings for P4.02~P4.04
0: no function
5: PID Feedback Signal
1: Frequency Command/PID Setpoint REMOTE (see P4.00)
6: PTC Thermistor Input Value
2: Frequency Command/PID Setpoint LOCAL (see P4.01)
7: PID Offset (Input)
3: Frequency Command/PID Setpoint REMOTE & LOCAL
8~10: reserved
4: reserved
11: PT100 Thermistor Input Value
User Display Settings for P8.00
0: Output Amps
11: AI1 %
21~24: reserved
1: Counter Value
12: AI2 %
25: Overload %
2: Actual Freq
13: AI3 %
26: Ground Fault %
3: DC Bus Voltage
14: IGBT Temperature
27: DC Bus Ripple
4: Output Voltage
15: Cap Temperature
28: PLC D1043 Value
5: Power Factor
16: DI Input Status
29: reserved
6: Output Power
17: DO Output Status
30: User-Defined
7: Calculated RPM
18: Multi-Speed Step
31: Out Hz x P8.05
8~9: reserved
19: CPU DI Status
32~33: reserved
10: PID Feedback %
20: CPU DO Status
34: Fan Speed
User Defined Format Settings for P8.02
Bi ts 4~9: User defined unit:
Bi ts 4~9: (continued)
000xh: Hz
001xh: rpm
002xh: %
003xh: kg
004xh: m/s
Bi ts 0~3:
005xh: kW
User defined decimal place:
006xh: hp
0000b: no decimal place
007xh: ppm
0001b: one decimal place
008xh: 1/m
0010b: two decimal place
009xh: kg/s
0011b: three decimal place
00Axh: kg/m
00Bxh: kg/h
00Cxh: lb/s
00Dxh: lb/m
00Exh: lb/h
00Fxh: ft/s
GS4_QSP_1edRevC 07/02/2021
Cooling and Heat Dissipation
33: LOCAL/REMOTE Selection
Model
34: Drive Enable
Number
External
35: Decel Energy Backup (DEB) Enable
36: PLC Mode select bit0
37: PLC Mode select bit1
GS4-21P0
38: Output MCR Auxiliary
14
GS4-22P0
Confirmation
14
39: reserved
GS4-23P0
40: Fire mode and force drive run
10
GS4-25P0
41: Fire mode and maintain operation
42: Disable all motors
40
GS4-27P5
43: Disable Motor #1
66
GS4-2010
44: Disable Motor #2
45: Disable Motor #3
58
GS4-2015
46: Disable Motor #4
166
GS4-2020
47: Disable Motor #5
48: Disable Motor #6
166
GS4-2025
49: Disable Motor #7
166
GS4-2030
50: Disable Motor #8
179
GS4-2040
179
GS4-2050
228
40: UVW Motor Contactor Enable
GS4-2060
41: DEB active
228
GS4-2075
42: Brake Released at Stop
43: RS485 Digital Output
246
GS4-2100
44: COM Card Digital Output
GS4-41P0
45: Fire Mode Indication
46: Fire Bypass Indication
GS4-42P0
47: Motor #1 Selected
14
GS4-43P0
48: Motor #2 Selected
49: Motor #3 Selected
10
GS4-45P0
50: Motor #4 Selected
10
GS4-47P5
51: Motor #5 Selected
52: Motor #6 Selected
40
GS4-4010
53: Motor #7 Selected
66
GS4-4015
54: Motor #8 Selected
55: Mtr1/Mtr2 Nameplate Parameters
58
GS4-4020
Select
99
56: Safety N.O. STO A
GS4-4025
57: Safety N.C. STO B
99
GS4-4030
58: Above Frequency Output (≥ P3.53)
126
59: Below Frequency Output (< P3.53)
GS4-4040
179
GS4-4050
179
GS4-4060
179
GS4-4075
186
GS4-4100
257
GS4-4125
223
GS4-4150
224
GS4-4175
35: reserved
289
GS4-4200
36: Carrier Frequency
37: reserved
GS4-4250
38: Drive Status
GS4-4300
39: reserved
40: reserved
41: kWh
42: PID Reference
43: PID Offset
44: PID Output Hz
• External Flow Rate is across the heat sink.
• Internal Flow Rate is through the chassis.
• Published flow rates are the result of active cooling using fans, factory
User defined unit:
installed in the drive.
011xh: m
• Unpublished flow rates ( - ) are the result of passive cooling in drives
012xh: ft
without factory installed fans.
013xh: °C
• The required airflow shown in the chart is for installing a single GS4 drive
014xh: °F
Bi ts 4~9: (continued)
in a confined space.
015xh: mbar
User defined unit:
• When installing multiple GS4 drives, the required air volume would be
016xh: bar
020xh: L/h
the required air volume for a single GS4 drive multiplied by the number
017xh: Pa
021xh: m3/s
of GS4 drives.
018xh: kPa
022xh: m3/h
019xh: mWG
023xh: gpm
01Axh: inWG
024xh: cfm
01Bxh: ftWG
01Cxh: psi
01Dxh: atm
01Exh: L/s
01Fxh: L/m
Airflow Rate for Cooling
Power Dissipation
Flow Rate (cfm)
Flow Rate (m
3
/hr)
Power Dissipation (Watt)
Loss External
Internal
Total
External
Internal
Total
(Heat sink)
–
–
–
–
–
–
33
–
14
24
–
24
56
–
14
24
–
24
79
–
10
17
–
17
113
14
54
68
24
92
197
14
80
112
24
136
249
14
73
99
24
124
409
12
178
282
20
302
455
12
178
282
20
302
549
12
178
282
20
302
649
30
209
304
51
355
913
30
209
304
51
355
1091
73
301
387
124
511
1251
73
301
387
124
511
1401
73
319
418
124
542
1770
–
–
–
–
–
–
33
–
–
–
–
–
–
45
–
14
24
–
24
71
–
10
17
–
17
103
–
10
17
–
17
134
14
54
68
24
92
216
14
80
112
24
136
287
14
73
99
24
124
396
21
120
168
36
204
369
21
120
168
36
204
476
21
147
214
36
250
655
30
209
304
51
355
809
30
209
304
51
355
929
30
209
304
51
355
1156
30
216
316
51
367
1408
73
330
437
124
561
1693
73
296
379
124
503
2107
112
336
381
190
571
2502
112
401
491
190
681
3096
454
771
–
–
–
454
771
• When calculating power
dissipation (Watt Loss), use the
Total value if the drive is foot
mounted, or the Internal value
if the drive is flange mounted.
Where only a total value is
published, these models cannot be
flange mounted. Heat dissipation
shown in the chart is for installing
a single GS4 drive in a confined
space.
• When installing multiple drives,
the volume of heat/power
dissipation should be the heat/
power dissipated by a single GS4
drive multiplied by the number of
GS4 drives.
• Heat dissipation for each model
is calculated by rated voltage,
current and default carrier
frequency.
Environment for Operation, Storage, and Transportation
DO NOT expose the GS4 drive to environments that contain dust, direct sunlight, corrosive/inflammable gases,
high humidity, liquids, or high vibration. The salt in the air must be less than 0.01 mg/cm
year.
Internal
Total
Installation Location
IEC60364-1/IEC60664-1 Pollution degree 2, Indoor use only
Storage: -25°C to +70°C
Surrounding
27
61
Temperature
Non-condensation, non-frozen
31
88
Operation: Max. 90%
36
115
Rated Humidity
No condense water
46
159
Air Pressure
Operation/Storage: 86 to 106 kPa
67
264
IEC721-3-3
86
335
Operation:
Pollution Level
Class 3C2; Class 3S2
121
529
No concentrate
161
616
If the GS4 drive is installed at altitudes of 0~1000m, follow normal operation
184
733
restriction. If installed at altitudes of 1000~3000m, decrease 1% of rated
Altitude
Operation
216
865
current or lower 0.5°C of temperature for every 100m increase in altitude.
Maximum altitude for Corner Grounded is 2000m.
186
1099
Storage
220
1311
Package
ISTA procedure 1A (according to weight) IEC60068-2-31
Transportation
Drop
267
1518
1.0mm, peak-to-peak value range from 2Hz to 13.2 Hz; 0.7G~1.0G range from 13.2Hz to 55Hz; 1.0G
308
1709
Vibration
range from 55Hz to 512 Hz. Comply with IEC 60068-2-6.
369
2139
IEC/EN 60068-2-27
Impact
25
59
Operation
Max. allowed offset angle ±10° (under normal installation position)
29
74
Position
33
104
38
141
Frame
Top cover
46
180
230V: 1.0~30HP With top cover removed Standard
76
292
A~C
460V: 1.0~40HP With top cover in place
93
380
230V: >30HP
122
518
D0~G
N/A
460V: >40HP
138
507
158
635
230V: >30HP
211
866
184
993
D0~G
N/A
218
1147
257
1413
460V: >40HP
334
1742
399
2092
491
2599
To prevent personal injury, please make sure that the case and wiring are installed according to these
579
3081
instructions. The figures in these instructions are only for reference. They may be slightly different from
687
3783
the one you have, but it will not affect your customer rights.
4589
These installation instructions may be revised without prior notice. The most recent edition can be
5772
downloaded from the AutomationDirect web site at any time:
http://www.automationdirect.com/static/manuals/index.html.
DURA
GS4 AC Drive Quick-Start Guide – 1st Ed, Rev.C 07/02/2021
pulse
2
throughout the
Transportation: -25°C to +70°C
Storage/Transportation: Max. 95%
Transportation: 70 to 106 kPa
Storage:
Transportation:
Class 2C2; Class 2S2
Class 1C2; Class 1S2
10°
10°
Operation
Conduit Box Protection Level
Temperature
IP20 / UL Open Type
-10~50°C
conduit plate
IP20 / UL Type1 / NEMA1
-10~40°C
With conduit
IP20 / UL Type1 / NEMA1
-10~40°C
box
IP00 / IP20 / UL Open Type
Only the circled area is IP00.
Other parts
are IP20.
Without
-10~50°C
conduit box
Page 5