DURApulse GS4 AC Drive Quick-Start Guide

Minimum Mounting Clearances

Frame A
GS4-21P0; GS4-41P0; GS4-22P0; GS4-42P0; GS4-23P0; GS4-43P0; GS4-25P0; GS4-45P0; GS4-47P5
Frame B
GS4-27P5; GS4-2010; GS4-4010; GS4-2015; GS4-4015; GS4-4020
Frame C
GS4-2020; GS4-2025; GS4-4025; GS4-2030; GS4-4030; GS4-4040
Frame D0 GS4-4050; GS4-4060
Frame D
GS4-2040; GS4-2050; GS4-4075; GS4-4100
Frame E
GS4-2060; GS4-2075; GS4-2100; GS4-4125; GS4-4150
Frame F
GS4-4175; GS4-4200
Frame G
GS4-4250; GS4-4300
(Blue Arrow) Inflow
(Red Arrow) Outflow
(Frame A~G)
Single drive:
Independent installation.
(Frame A, B, C, G)
Multiple drives:
Independent horizontal installation.
(Frame D0, D, E, F)
Multiple drives:
Independent horizontal installation.
Install a barrier between the drives.
(Frame A~G)
Multiple drives:
Independent installation.
Ta: Frame A~G
(inflow air temperature)
It is suggested to install a barrier
between the drives. Adjust
the size of the barrier until the
temperature of the fan on the
inflow side is lower than the
operation temperature. This barrier
is to prevent the lower drives' hot
exhaust from going straight into
the upper drives' intake.
(Refer to the right figure)
Operation temperature is the
temperature measured 50mm away
from the inflow side of the fan.
GS4_QSP_1edRevC 07/02/2021
Minimum Mounting Clearance
Frame
A (mm / in)
B (mm / in)
A~C
60 / 2.4
30 / 1.2
D0~F
100 / 4.0
50 / 2.0
G
200 / 7.9
100 / 4.0
Note:
• The mounting clearances shown in figure to the left are NOT for installing the
GS4 drive in a confined space (such as cabinet or electric box). When installed in
a confined space, in addition to the minimum mounting clearances, ventilation
equipment or air conditioning should be installed to keep the surrounding
temperature lower than the operation temperature.
• The following table shows heat dissipation and required air volume when installing
a single GS4 drive in a confined space. When installing multiple drives, the required
air volume shall be multiplied by the number of GS4 drives.
• Refer to the chart (Air flow rate for cooling) for ventilation equipment design and
selection.
• Refer to the chart (Power Dissipation) for air conditioner design and selection.
• If GS4 drives in frames sizes A thru D are installed with clearance dimensions less
than specified, the cooling fans in these models may not adequately cool the drive.
Specifications for Wiring Terminals – Main-Circuit Terminals
Max Wire
Min Wire
Torque
Drive Models
Note
Gauge
Gauge
(±10%)
14 AWG
UL installations must use 600V, 75°C or 90°C wire.
GS4-21P0
(2.1 mm
2
)
Please use copper wire only.
12 AWG
(Fig. 1) The usage of ring terminals should comply
GS4-22P0
(3.3 mm
2
)
with this specification.
(Fig. 2) The figure shows the specification of insulated
10 AWG
GS4-23P0
heat shrink tubing that complies with UL
(5.3 mm
2
)
(600C, YDPU2).
8 AWG
GS4-25P0
(8.4 mm
2
)
M4
Figure 1:
8 AWG
20 kg·cm
GS4-41P0
(8.4 mm
2
)
(17.4 lb·in)
14 AWG
GS4-42P0
(1.96 N·m)
(2.1 mm
2
)
GS4-43P0
GS4-45P0
10 AWG
(5.3 mm
2
)
GS4-47P5
Terminal D+[+2 & +1]: Torque 45 Kg·cm [39.0 lb·in]
8 AWG
GS4-27P5
(4.415 N·m) (±10%)
(8.4 mm
2
)
Use 600V, 90°C wire for UL installation of GS4-2015
6 AWG
install if ambient temperature exceeds 45°C.
GS4-2010
(13.3 mm
2
)
UL installations of other models must use 600V, 75°C
4 AWG
or 90°C wire. Please use copper wire only.
GS4-2015
(21.2 mm
2
)
(Fig. 1) The usage of ring terminals should comply
with this specification.
GS4-4010
8 AWG
(Fig. 2) The figure shows the specification of insulated
(8.4 mm
2
)
GS4-4015
heat shrink tubing that complies with UL
M5
(600C, YDPU2).
4 AWG
35 kg·cm
(21.2 mm
2
)
(30.4 lb·in)
Figure 1:
(3.43 N·m)
6 AWG
GS4-4020
(13.3 mm
2
)
Specifications for Wiring Terminals – Main-Circuit Terminals (continued)
Max Wire
C (mm / in)
D (mm / in)
Drive Models
Gauge
10 / 0.4
0 / 0
n/a
0 / 0
GS4-2020
n/a
0 / 0
GS4-2025
GS4-2030
GS4-4025
GS4-4030
1/0 AWG
(53.5 mm
2
)
GS4-4040
For models without conduit box
GS4-4050
2/0 AWG
(67.4 mm
2
)
GS4-4060
Figure 2:
For models with conduit box
GS4-4050
2/0 AWG
(67.4 mm
2
)
GS4-4060
For models without conduit box
Figure 2:
GS4-2040
GS4-2050
300 MCM
(152 mm
2
)
GS4-4075
GS4-4100
For models with conduit box
GS4-2040
GS4-2050
4/0 AWG
(107 mm
2
)
GS4-4075
GS4-4100
DURA
GS4 AC Drive Quick-Start Guide – 1st Ed, Rev.C 07/02/2021
pulse
Min Wire
Torque
Note
Gauge
(±10%)
Terminal D+[+2 & +1]: Torque 90 Kg-cm [78.2 lb-in.]
1 AWG
(8.83Nm) (±10%)
(42.4 mm
2
)
Use 600V, 90°C wire for UL installation of GS4-2030
1/0 AWG
install if ambient temperature exceeds 40°C.
(53.5 mm
2
)
UL installations of other models must use 600V, 75°C
or 90°C wire. Please use copper wire only.
4 AWG
(Fig. 1) The usage of ring terminals should comply
(21.2 mm
2
)
with this specification.
(Fig. 2) The figure shows the specification of insulated
heat shrink tubing that complies with UL (600C,
M8
YDPU2).
80 kg·cm
Figure 1:
Figure 2:
(69.4 lb·in)
(7.85 N·m)
2 AWG
(33.6 mm
2
)
UL installations must use 600V, 75°C or 90°C wire.
Please use copper wire only.
1/0 AWG
(Fig. 1) The usage of ring terminals should comply
(53.5 mm
2
)
with this specification.
(Fig. 2) Ground wire spec: 2AWG*2 [33.6mm
2
(Fig. 3) The figure shows the specification of insulated
2/0 AWG
heat shrink tubing that complies with UL
(67.4 mm
2
)
(600C, YDPU2).
Figure 1:
Figure 2:
8.2 Min.
22 Max.
Ring lug
8.2 Min.
Ring lug
M8
81.6 kg·cm
(70.8 lb·in)
(8N·m)
1/0 AWG
Figure 3:
(53.5 mm
2
)
Heat Shrink Tube
Heat Shrink Tube
WIRE
WIRE
UL installations must use 600V, 75°C or 90°C wire.
4/0 AWG
Please use copper wire only.
(107 mm
2
)
(Fig. 1) The usage of ring terminals should comply
250 MCM
with this specification.
(127 mm
2
)
(Fig. 2) The figure shows the specification of insulated
heat shrink tubing that complies with UL
3/0 AWG
(600C, YDPU2).
(85mm
2
)
300 MCM
Figure 1:
Figure 2:
M8
(152 mm
2
)
200 kg·cm
(173 lb·in)
(19.62 N·m)
3/0 AWG
(85 mm
2
)
4/0 AWG
(107 mm
2
)
2/0 AWG
(67.4 mm
2
)
4/0 AWG
(107 mm
2
)
*2]