Dynalite DMC810GL Installationshandbuch - Seite 10
Blättern Sie online oder laden Sie pdf Installationshandbuch für Controller Dynalite DMC810GL herunter. Dynalite DMC810GL 12 Seiten. Leading edge dimmer/hf ballast controller
.........................................................................................................................
Check the following list. If you are still unable to rectify the situation, contact your nearest Dynalite office. A complete list of
distributors worldwide can be found on the Internet at: http://dynalite-online.com/html/contacts.htm. Please ensure that you
have completed the following prior to calling our technical support department.
Check all symptoms in the Troubleshooting list
Check for any deviations between the installation and the installation instructions
Make a list of the model numbers of all devices used in the system
SYMPTOM
Dimmer does not operate at all. No Service LED
activity. Power supply indicator LED on PCB not lit.
Power supply indicator LED lit, but no Service LED
activity.
Dimmer will not respond to control panel push
buttons.
Dimmer operates properly but circuit breakers keep
tripping.
Fluorescent lights won't dim.
specification
.........................................................................................................................
Regulating Device:
Switching Device:
Power Conditioning;
Interference Suppression:
Control Inputs:
User Controls:
Internal Controls:
DyNet DC Supply:
Preset Scenes:
Supply Terminals:
Output Terminals:
Cable Entries:
Diagnostic Functions:
(DTK600, DLight or BAS interface required
for displaying and analysing diagnostic data)
Compliance:
Ambient Temperature:
Construction:
Dimensions:
.........................................................................................................................
PROBABLE CAUSE
Incorrect connection of mains supply, or no
power available.
Supply voltage too low, short circuit on
network. Control PCB faulty.
Control panel incorrectly wired or incorrect
configuration.
Instant tripping: - short circuit on load.
Delayed tripping: - dimmer overloaded.
Wrong type of ballast or ballast incorrectly
wired.
Supply:
230V ±14% 50/60Hz Single Phase at 40A
Outputs:
4 x 10A dimmed (leading edge phase control) outputs
4 x 10A switched outputs
4 x HF ballast control outputs selectable to DALI Broadcast, 1-10V DC, DSI
Protection:
4 x 10A 6kA single pole thermal magnetic circuit breakers
Triac 600V, 40A nom. 400A surge
Relay 16A nom. (resistive), Fluorescent 800A surge, Incandescent 165A surge,
Regulated outputs
Over voltage protection
Surge protection
Brownout/Sag protection
Spike protection
Soft Start
Iron powder toroidal choke
Rise Time:
100S at 230V
1 x RS485 DyNet/DMX512 serial port
1 x programmable dry contact AUX input
Service Switch
Diagnostic LED
Programmable Logic Controller
Dynalite Accessory Module enabled
200mA
170
Line, Neutral – 2 x 10mm
Line, Neutral for each channels 1-8
2
2 x 4mm
max conductor size
Earth link bar provided
0V/DSI/DALI, +V/DSI/DALI for channels 9-12
2
1 x 2.5mm
max conductor size
Mains – 8 x 25mm dia. knockout
Data – 1 x 25mm dia. knockout
Device Online/Offline status
Circuit breaker trip reporting (optional)
Circuit run time tracking
CE, C-Tick, RCM
40C max.
Alloy/Steel wall mount case with epoxy finish
Height 370mm x Width 215mm x Depth 170mm (excludes wall brackets)
Weight:
7.5 Kilograms
ACTION
Check power supply to dimmer. Check Line and
Neutral input connections.
Check supply voltage is at least 75% of rated
voltage.
Disconnect network bus and restore power.
Replace control PCB.
Check operation of LEDs on control panel. Push
button on panel and study response of service
LED.
Check load wiring for short circuits.
dimmer loading with current tester (don't forget to
de-rate
transformer losses). Check that the breaker
terminals are tight.
Check ballast type. Check actual wiring against
ballast manufacturer's diagram.
10V/DSI, DALI Broadcast settings.
2
max conductor size
DMC810GL Instruction Manual Rev B.DOC
troubleshooting
Check
12V
terminal
voltages.
for
low
power-factor
loads
Check 1-
Verify
and
10