Autonics PSQ-C01 Series Datenblatt - Seite 12
Blättern Sie online oder laden Sie pdf Datenblatt für Messgeräte Autonics PSQ-C01 Series herunter. Autonics PSQ-C01 Series 14 Seiten. Dual lcd display digital pressure sensor
PSQ Series
Output type change
Output type for OUT1 and OUT2 can be able to set Nor-
mally Open or Normally Closed.
※ Note that Normally Open and Normally Closed provide
opposite output.
SV
OUT1 output
Normally Open
NO
Normally Closed
NC
Normally Open
1O2O
Normally Open
1O2C
Normally Closed
1C2O
Normally Closed
1C2C
Response time (chattering prevention)
It can prevent control output from chattering by changing
response time.
There are 10 types of response time; 2.5ms, 5ms, 10ms,
25ms, 50ms, 100ms, 250ms, 500ms, 1,000ms, 5,000ms.
If the response time is getting longer, the detection will be
more stable by increasing the number of digital filter.
PV display color and color linked output
You can select PV display color to the linked output status.
There are 4 types as below.
Select color linked output among [OUT1], [OUT2], or [ALL].
SV
PV display color
Green in normal status. When the set color linked output
R-ON
turns ON, it displays red.
Red in normal status. When the set color linked output
G-ON
turns ON, it displays green.
Red is fixed.
RED
Green is fixed.
GREN
Pressure unit change
PSQ series has 8 kinds of pressure unit.
Please select the proper unit for application.
• kPa, MPa, kgf/cm
2
, bar, psi, mmHg, inHg, mmH
※ When using mmH
O unit, multiply display value by 100.
2
SV display part
Select the display type at the SV display part in RUN mode.
There are 3 types; displaying SV [STD], displaying unit
[UNIT], none [OFF]
RESET
This function is to reset all parameters as factory default
except control output SV to prevent wrong settings or
difficult operation.
Password
This function is to limit parameter settings, to check the
parameter or to change the parameter settings only for
entering the set password.
• 0000: Password function OFF
• 0001: Only checking parameters
• Setting range: 0002 to 9999
G-20
OUT2 output
OFF
OFF
Normally Open
Normally Closed
Normally Open
Normally Closed
O
2
Control output change
Select between NPN open collector output or PNP open
collector output.
Key lock
The key lock function prevents key operations so that
conditions set in each mode.
ᆞPress the
key over 1 sec in RUN mode to lock
+
M
keys. The PV display part displays [LOCK], and the SV
display part displays [ON] for 1 sec and it returns in RUN
mode.
ᆞPress the
key over 1 sec in RUN mode to unlock
+
M
keys. The PV display part displays [LOCK], and the SV
display part displays [OFF] for 1 sec and it returns in
RUN mode.
Zero-point adjustment
The zero-point adjustment function forcibly sets the
pressure value to "zero" when the pressure port is opened
to atmospheric pressure. When the zero adjustment is
applied, analog output [Voltage or Current] is changed by
this function.
To set zero atmospheric pressure forcibly,
press the
keys over 1 sec in RUN mode with the
+
opened pressure port.
High/Low Peak Hold
This function is to diagnose malfunction of the system
caused by parasitic pressure through memorizing input the
max./min. pressure occurred from the system.
Press the
key more than 1 sec in RUN mode and set
+
M
the
Peak Hold.
Error and troubleshooting
Display Cause
When adjusting zero point
while external pressure is
ERR1
input.
When over current is
ERR2
applied on control output
When the range of Auto
sensitivity setting mode
ERR3
ST1, ST2 is set incorrectly.
When connection between
master and slave is wrong
ERR4
during copying parameters.
When entering invalid
ERR5
password.
When applied pressure
exceeds the high-limit of
HHHH
display pressure range.
When applied pressure
exceeds the low-limit of
LLLL
display pressure range.
When the correction value
of auto shift, remote zero
-HH-
exceeds the high-limit of
the setting range.
When the correction value
of auto shift, remote zero
-LL-
exceeds the low-limit of the
setting range.
-HL- When [HH], [LL] occur both.
Troubleshooting
Try again after removing
external pressure.
Remove the over current
conditions by adjusting load
resistance.
Check the setting range and
set ST1, ST2.
Check the cables between
sensors and the connection
of the same models.
Enter valid password.
Apply pressure within the
display pressure range.
Set the correction value
of auto shift, remove zero
within the setting range.