DynaQuip WaterCop WROPE6 Benutzerhandbuch und Installationshandbuch - Seite 7

Blättern Sie online oder laden Sie pdf Benutzerhandbuch und Installationshandbuch für Kontrollsysteme DynaQuip WaterCop WROPE6 herunter. DynaQuip WaterCop WROPE6 16 Seiten.

DynaQuip WaterCop WROPE6 Benutzerhandbuch und Installationshandbuch

To Power and Program Wireless Sensors

WaterCop® Pro wireless sensors are addressable . This means that the WaterCop® Pro Water
Control Panel can tell you the operational status of each wireless sensor . If you have many
wireless sensors, this feature will quickly tell you where the leak is located or warn you if a sensor
requires service (low batteries) . It is important that you introduce each wireless sensor to
the WaterCop® Pro Water Control Panel and document the sensor (the transmitter and the
sensor probe together; not just the probe) number on the transmitter. Once placed in location,
you will also note this information on the Sensor Location Log (available as a PDF file) .
Once the wireless sensors are programmed, you will be able to place them in desired locations
to monitor the property for water intrusion .

Powering Wireless Sensors

WaterCop® Pro wireless sensors require power to operate . Use either fresh AAA alkaline
batteries (not included) and/or a WaterCop® Pro Sensor AC Adapter (sold separately) to power . If
both are used, batteries will provide back-up power in the event AC power is lost . Rechargeable
batteries are not recommended . To install batteries, remove the battery cover located on
the back of the sensor, and install batteries in accordance with the (+ and -) placement guide .
Reinstall back plate .
It is important that you number each sensor (not each sensor probe) for easy identification
while programming . The WaterCop® Pro System is capable of supporting as many as 45
wireless sensors . Wireless sensors, up to 45 total, can be added in the future by repeating the
steps taken in this section . Please contact your local dealer or DynaQuip® Controls to inquire
about additional sensors .
Once each sensor is powered and numbered, you are ready to begin programming the
sensors to the WaterCop® Pro Water Control Panel .
Programming Hardwired Sensor Probes for the Hardwired Water Control Panel
First, while the power is off install all sensor probes .
Connect the power to the Water Control Panel .
Short each probe using a conductive metal surface until the display reads "WIREPANEL SHT"
and the corresponding light on the side of the panel lights up .
Repeat for all sensor probes .
Programming Wireless Sensors WPM
Plug the WaterCop® Pro Control Panel power supply into a nearby 115 VAC outlet . Depending
upon the position of the valve, the Actuator may initially turn the valve when first powered .
You can also program sensors while leaving the jumpers in instead . Unplug the Control Panel
before removing them and wiring in the Pro Actuator .
BE EXTREMELY CAREFUL TO KEEP FINGERS AND OTHER ITEMS OUT OF THE VALVE.
The display will read WaterCop® NORMAL .
To add sensor #1, Press MODE twice (DEVICE ADD will display on the LCD) .
Press CLOSE once (DEV #1 ID= will display on the LCD) .
Press and hold the LEARN button inside the WPM . The sensor will beep and the LCD will
display SEN #1 SHORT 2, then release the LEARN button and LCD will display DEVICE
STATUS SEN #1 OK!
To add sensors #2 through #45: If time has passed, the Water Control Panel LCD will revert
to ready mode displaying WaterCop® NORMAL . To add more sensors, you will need to
return to program mode and repeat steps used to add sensor #1 .
Repeat above steps for all of your wireless sensors, taking care to program them in the same
order as labeled . When finished, Press MODE three times to return to the NORMAL mode .
7