FM
12
MODBUS
HOLDING REGISTERS
Description
Mode setting
Fan speed setting
Louver swing setting
Setting temperature
Address setting
Reset
Week
Hour
Minute
Second
Hours in Timer on
Minute in Timer on
Hours in Timer on
Minute in Timer on
Icon of Timer ON or OFF
Super low speed rpm
Low speed rpm
Medium speed rpm
High speed rpm
RPM setting
Temperature sampling time
Factor of auto fan speed
Factor of modulating valve
FC66003740 - Rev 01
Address
300000
300001
300002
300003
300004
300005
300006
300007
300008
300009
300010
300011
300012
300013
300014
310000
310001
310002
310003
310004
310005
310006
310007
All copying, even partial, of this manual is strictly forbidden
Type
Remark
Cooling mode= 01(H)
Humidify mode= 02(H)
R/W
Fan mode= 04(H)
Heating mode= 08(H)
Auto mode= 10(H)
Low speed= 04(H)
Medium speed= 02(H)
R/W
High speed= 01(H)
Auto fan speed= 07(H)
Position 1= 01(H)
Position 2= 02(H)
Position 3= 03(H)
R/W
Position 4= 04(H)
Auto= 0F(H)
Stop= 00(H)
R/W
16~30 degree C (actual*10 format)
R
Set by dip-switch, reading only
W
= 0x33 reset error
W
Calibration wired wall pad and set timer function
W
Calibration wired wall pad and set timer function
W
Calibration wired wall pad and set timer function
W
Calibration wired wall pad and set timer function
R/W
Timer ON
R/W
Timer ON
R/W
Timer OFF
R/W
Timer OFF
BIT0= Icon of Timer ON
BIT1= Icon of Timer OFF
R/W
1= enable
0= disable
R/W
200~1500
R/W
200~1500
R/W
200~1500
R/W
200~1500
R/W
200~2000 (used to test, 0=disable)
R/W
2~100, default:5S
R/W
2~150, default:20
R/W
2~250, default:150
17