Step-by-step
9
Continue the VibraClean radiator
agitation to dislodge any sludge
deposits until the return hose to the
RapidFlush filter runs clear.
Isolate and clean the RapidFlush filter
10
as required. Using Personal Protective
Equipment i.e. gloves and paper towels,
wipe off any magnetite into a bucket.
Waste should be bagged and thrown
away. When satisfied, open up the
next radiator, turn off the treated
radiator and repeat the process until all
radiators are clean.
Sludge removal tool available at
adeyspares.co.uk.
11
You will need flexible hoses with isolators.
Remember to double check valve, pressure
reducing valve and gauge. Isolate electrics to
the boiler and set the boiler control to OFF.
Attach a drain hose to the MagnaCleanse
drain valve and secure with a jubilee clip. When
cold, temporarily cap off the expansion pipe.
Temporarily connect the cold mains supply and
tank cold feed supply (to bypass header tank)
including a combined stop tap and pressure
gauge to control the water pressure.
Bypass expansion heating tank as shown
opposite (fittings not supplied). This is a
temporary basis for the cold flush of the
flushing process ONLY. The blank vent
pipe is a temporary measure during cold
flush ONLY. Never blank vent pipes for any
other reason. HEATING BOILER MUST
BE OFF and ISOLATED FOR THE COLD
FLUSH. Set pressure reducing valve to
under 1 bar pressure before commencing
cold flush. Caution: Do not over pressurize
existing heating system during cold flush.
Remember to double check valve, pressure
reducing valve and gauge.
Cold main
Cold feed
Remember to monitor the
MagnaCleanse system
throughout operation.