5. General standard

1. Maximum faulty operation protection voltage between input terminal
and earthing is 600V.
2. Maximum overload protection for clamp head terminal:100A.
3. Maximum display: 2000 Counts, update 2~3 times per second.
Over range displays "OL".
Diode: approx. 3.2V
Range: automatic (exclusive of electricity gear)
Polarity: automatic
Work temperature: 0°C ~40°C
Relative humidity: 0°C ~30°C :75%,30°C ~40°C :50%
Storage temperature: -10°C~50°C
4. Electromagnetic compatibility:
In 1V/m radio frequency field: overall frequency=designated precision
+5%, radio frequency field above 1V/m has no designated index.
5. Work altitude: 0~2000m
6. Built-in battery: AAA 1.5V x 2 pieces
7.
Low battery: LCD displays "
8. Dimensions: approx. approx. (175 x 60 x 33.5mm), maximum clamp
head size is 17mm.
9. Weight: approx. 170g (including battery)

6. Product panel figure

1. Clamp head.
2. Protective barrier.
3. Clamp head trigger: pull the trigger to open clamp head.
4. NCV indicator: when the induced AC electric field intensity and
induction distance satisfy designated value, it will send out warning
sound and flashes.
5. Function selection button: rotate this button to switch to corresponding
functions indicated on the panel.
6. HOLD/backlight key: for measuring readings/long press 2s to turn on
or turn off backlight.
7.
ZERO key: used for DCA zero, capacitance/voltage measurement
relative value.
8. SELECT key: select function mode, such as ACV/DCV, resistance/ on-
off/diode/capacitance, ACA/DCA, etc. in AC voltage and current gear,
long press this key for more than 2s to enter or exit VFC function.
9. LCD display screen: measurement function, symbol and numerical
value.
6
".