ELECTRICAL CONNECTION
IMPORTANT INFORMATION FOR ELECTRICIANS
• It is possible to connect in parallel electronic motors to a switch in
residential applications where the total power cable length does
not exceed 10 meters. The number of motors paralleled together
is limited to 4-5 according to the switch total amperage capacity.
• Electronic motors cannot be paralleled connected together
when controlled by a Building Management system (BMS).
• Compatibility between electronic motors and BMS must be
approved and tested by manufacturer of BMS.
• For standard motor operation only a standard switch allowing either
UP or DOWN but not both at the same time must be used. Only
mechanically or electrically interlocked switches can be used.
• Motors with electronic limits can be connected in parallel. The
maximum load of the switch must never be exceeded.
• When changing from UP to DOWN or vice versa, the switchover time
must at least be 0.5 seconds and effected through an OFF position.
Only switches with a defined neutral position or one with a built-in
switching delay should be used.
• An "active path" control unit which monitors the current draw is in
conflict with the motor and cannot be used.