Allied Motion TCI V1K Kit Installationshandbuch

Blättern Sie online oder laden Sie pdf Installationshandbuch für Water Filtration Systems Allied Motion TCI V1K Kit herunter. Allied Motion TCI V1K Kit 2 Seiten.

General Safety Instructions
Warning
Be sure to read, understand, and follow all safety
!
instructions.
Warning
Only qualified electricians should carry out all
electrical installation and maintenance work on
!
V1K drive output filters.
Warning
All wiring must be in accordance with the National
Electrical Code (NEC) and/or any other codes that
!
apply to the installation site.
Warning
Disconnect all power before working on the
equipment. Do not attempt any work on a powered
V1K output filter.
Warning
The V1K, VFD, motor, and other connected
equipment must be properly grounded.
The VFD terminals and connected cables are at a
Warning
dangerously high voltage when power is applied to
the VFD, regardless of motor operation.
Installation Checklist
• Access V1K installation drawings on the TCI website
for unit dimensions, mounting hole pattern, mounting
orientation, wire locations, unit weights, and other
unit specific installation notes.
https://transcoil.com/
products/v1k-motor-protection-filter/
• Ensure installation location is not exposed to corrosive
liquids or gases, explosive or combustible gases or
dust, excessive airborne dirt and dust, or excessive
vibration.
• Select mounting area that allows adequate cooling air
and maintenance access.
• Ensure all wiring conforms to requirements of the
National Electric Code (NEC) and\or other applicable
electrical codes.
• Ground V1K output filter to a dedicated system
ground to ensure safety and filter performance. Use
properly sized grounding conductor.
• Wire output power terminals of the VFD to the input
terminals of the V1K: U, V, & W.
• Wire the output power terminals of the V1K, T1, T2, &
T3 to the motor power connections.
• Ensure VFD is set for operating modes and ranges
that are compatible with the V1K.
• Check entire system thoroughly before energizing and
operating any equipment.
When you receive the unit, immediately inspect the
shipping container and report any damage to the
shipping carrier who delivered the unit.
Field Wiring Connection Terminals
Compression type terminals are available for all line wiring
connections. The wire size capacity ranges and tightening
torque for the reactor power terminals are listed in the
table.
Reactor Terminal Block/
Optional Lug Kit Terminals
V1K Kit
Current
Part Num.
Rating
Wire Size
V1K2A0K
2
12 - 14 AWG
V1K3A0K
3
12 - 14 AWG
V1K4A0K
4
12 - 14 AWG
V1K6A0K
6
12 - 14 AWG
V1K8A0K
8
12 - 14 AWG
V1K12A0K
12
12 - 14 AWG
V1K16A0K
16
4 - 12 AWG
V1K18A0K
18
4 - 12 AWG
V1K21A0K
21
4 - 12 AWG
V1K25A0K
25
4 - 8 AWG
V1K27A0K
27
4 - 8 AWG
V1K35A0K
35
6 - 8 AWG
V1K45A0K
45
6 AWG
V1K55A0K
55
1 - 4 AWG
V1K80A0K
80
1 - 3 AWG
V1K110A0K 110
2/0 - 1/0 AWG
V1K130A0K 130
2/0 AWG
V1K160A0K 160
250 kcmil - 3/0 AWG
V1K200A0K 200
(2) 2/0 - 1 AWG
V1K250A0K 250
(2) 2/0 AWG
V1K305A0K 305 (2) 350 kcmil - 3/0 AWG
V1K362A0K 362 (2) 350 kcmil - 4/0 AWG
V1K420A0K 420
(2) 600 - 300 kcmil
V1K480A0K 480
(2) 600 - 350 kcmil
V1K600A0K 600
(2) 600 - 500 kcmil
V1K750A0K 750
(3) 600 - 400 kcmil
All electrical connections must be re-torqued annually.
See www.transcoil.com for component drawings and dimensions.
Please contact TCI Technical Support or your TCI distributor for
application information regarding the use of V1K output filters on
the output side of the VFD.
TCI, LLC
W132 N10611 Grant Drive,
Germantown, Wisconsin 53022
800-824-8282 | www.transcoil.com
Board
Lug
Part
Kit
Torque
Num.
Installation Guide
(lb-in)
10
25009
N/A
10
25009
N/A
10
25009
N/A
10
25009
N/A
Product Specifications
10
25009
N/A
• Current Rating: 2 - 750 Amps, 208 V - 600 V, .75 - 600 HP
10
25009
N/A
• UL Listed
20
25009
N/A
• Efficiency > 98%
20
25009
N/A
• Insulation Rating: 600V Class
20
25009
N/A
• Insulation Class: Class H (180°C or better)
20
25009
N/A
• Maximum Altitude: 2000 m (6,000 ft) Derating necessary
20
25009
N/A
above 2000 m
30
25011
N/A
• Lead Length: up to 1,000 ft (Specific applications could
30
25011
N/A
reach longer lead lengths.)
35
25011
N/A
• Ambient Temp: Min -25°C, Max 40°C
35
25011
N/A
• For use with three phase VFDs operating at 2 kHz - 4 kHz
50
25011 SLK10
PWM carrier frequency and with a maximum motor cable
50
25011 SLK10
size necessary to achieve a 5% voltage drop at 1,000 ft.
375
25012 SLK21
• Optional thermal switch electrical rating: 120 V/6 A
50
25012 SLK22
• Switch opens on temperature rise
50
25012 SLK22
• 2 A to 12 A standard 195°C trip
375
25012 SLK13
• 2 A to 12 A EX version 160°C trip
375
25012 SLK13
• 16 A to 110 A 160°C trip
500
25012 SLK14
500
25012 SLK14
500
25012 SLK14
500
25012 SLK16
Revision 1.0
V1K Kit
Wiring Diagram
TCI, LLC
W132 N10611 Grant Drive,
Germantown, Wisconsin 53022
800-824-8282 | www.transcoil.com
Part # 31259
06/06/2022