Chromalox RTPC Einbauanleitung
Blättern Sie online oder laden Sie pdf Einbauanleitung für Kabel und Anschlüsse Chromalox RTPC herunter. Chromalox RTPC 4 Seiten. Power connection kit for self-regulating & constant wattage heating cables
Auch für Chromalox RTPC: Installationsanleitung Handbuch (8 seiten)
RTPC Power Connection Kit for Self-Regulating
and Constant Wattage Rapid-Trace Heating Cable
ELECTRIC SHOCK HAZARD. Disconnect all power
before installing or servicing heating cable and
accessories. A qualified person must perform
installation and service of heating cable and
accessories. Heating cable must be effectively
g r o u n d e d i n a c c o r d a n c e w i t h t h e N a t i o n a l
Electrical Code. Failure to comply can result in
personal injury or property damage.
NOTE: All electrical wiring, including GFCI (Ground Fault
Circuit Interrupters), must be done according to National
Electrical or local codes by a qualified person.
The RTPC Kit is used to connect base, braided (-C) and over-
coated (-CR or -CT) versions of Self-Regulating and Fluoropolymer
insulated Constant Wattage Rapid-Trace Heating Cables to power.
© 2010 Chromalox, Inc.
Chromalox
Installation Instructions
RTPC Power Connection Kit Parts:
1 - Molded Junction Box consisting of:
Base - Box - Lid - Hardware
1 - Three Position Terminal Block
1 - Mounting Screw for Terminal Block
®
SERVICE REFERENCE
DIVISION
SALES
REFERENCE
DATE
1 - Black Cable Grommet
1 - Orange Cable Grommet
1 - Cover Gasket
GENERAL
The cable grommet is furnished with this kit, such that the black
grommet is used for self-regulating cables SRL, SRF, SRM/E,
SRL/S, SRMF/S and the orange grommet is used for constant
wattage cable CWM and self-regulating cable SRS.
Each kit contains enough material to make one power connec-
tion point. It is possible to connect up to three Self-Regulating or
two Constant Wattage Cables in the same box. (One grommet
required for each cable.)
Materials required for installation include: standard electrical
cutters, screwdriver, sharp utility knife and a pipe strap
(Chromalox PS or equal).
Wipe inside lip of cover with a clean cloth. Remove protective
backing from the gasket and affix it to the cover lip. Press firmly
all around for proper adhesion.
4
RT
SECTION
(Supersedes PJ451-10)
161-562762-001
MARCH, 2009
PJ451-11