2.2
DIL SWITCH SETTINGS
The following table is to illustrate the various options available for relay and timer operations, see also fig.
3: -
DIL switch
Switch OFF: (pushed to the left)
number
Switch 1:
Relay 1 energised when probes E and B
(at the top)
are wet.
Switch 2:
Relay 1 energises after timer has
expired. (delay on)
Switch 3:
Set switch 3 to OFF to use 2 probes (E
and B) with timer function.
Switch 4:
Audible alarm (optional extra) sounds
when relay 1 operates.
Switch 5:
Relay 2 (where fitted) energised when
probes E and D are wet.
Switch 6:
Relay 2 (where fitted) energises after
timer has expired. (delay on)
Switch 7:
Set switch 7 to OFF to use 2 probes (E
and D) with timer function.
Switch 8:
Low sensitivity for normal tap water.
(at the bottom)
3.
DISPOSAL
Disposal of this product or parts of it must be carried out in accordance with the following guidelines:
Use the local public or private recycling/waste collection service.
In case such a recycling/waste collection service does not exist or cannot handle the materials used in
this product, please deliver the product or any hazardous material from it to your nearest AquaTech-
Pressmain office.
We, Aquatech-Pressmain Limited, declare this
LSM LIQUID LEVEL SWITCH
MODELS:LSM, LSM-P3 & LSM-TT-B
when installed and used in accordance with the instruction manual provided is in conformity with
the following standards:
BS EN 60204-1:2006, BS 61000-6-1:2001, BS 61000-6-3:2001
following provisions of EEC Directives:
Electro Magnetic Compatability Directive 89/336/EEC with amendments 92/31/EEC.
AGM House, London Rd, Copford, Colchester, Essex CO6 1GT UK
Aquatech-Pressmain Limited Instruction manual\Liquid Level Switch LSM
EC Declaration of Conformity
Low Voltage Directive 73/23/EEC and 93/68/EEC,
I.D.Taylor, I.Eng.MIET. Director, AquaTech-Pressmain Limited.
AquaTech-Pressmain Limited
Telephone: 01206 215121 Fax: 01206 215131
Switch ON: (pushed to the right)
Relay 1 energised when probes E and B
are dry.
Relay 1 releases after timer has expired.
(delay off)
Set switch 3 to ON to use 3 probes (E, A
& B) without timer function.
Audible alarm (optional extra) sounds
when relay 2 operates.
Relay 2 (where fitted) energised when
probes E and D are dry.
Relay 2 (where fitted) releases after timer
has expired. (delay off)
Set switch 7 to ON to use 3 probes (E, C
& D) without timer function.
High sensitivity for fluids with low
conductivity (purer water).
12.11.04
Level Switch LSM
12