AQUATECH LSM Instrukcja obsługi - Strona 12

Przeglądaj online lub pobierz pdf Instrukcja obsługi dla Przełącznik AQUATECH LSM. AQUATECH LSM 12 stron. Level switch

AQUATECH LSM Instrukcja obsługi
2.2

DIL SWITCH SETTINGS

The following table is to illustrate the various options available for relay and timer operations, see also fig.
3: -
DIL switch
Switch OFF: (pushed to the left)
number
Switch 1:
Relay 1 energised when probes E and B
(at the top)
are wet.
Switch 2:
Relay 1 energises after timer has
expired. (delay on)
Switch 3:
Set switch 3 to OFF to use 2 probes (E
and B) with timer function.
Switch 4:
Audible alarm (optional extra) sounds
when relay 1 operates.
Switch 5:
Relay 2 (where fitted) energised when
probes E and D are wet.
Switch 6:
Relay 2 (where fitted) energises after
timer has expired. (delay on)
Switch 7:
Set switch 7 to OFF to use 2 probes (E
and D) with timer function.
Switch 8:
Low sensitivity for normal tap water.
(at the bottom)
3.

DISPOSAL

Disposal of this product or parts of it must be carried out in accordance with the following guidelines:
Use the local public or private recycling/waste collection service.
In case such a recycling/waste collection service does not exist or cannot handle the materials used in
this product, please deliver the product or any hazardous material from it to your nearest AquaTech-
Pressmain office.
We, Aquatech-Pressmain Limited, declare this
LSM LIQUID LEVEL SWITCH
MODELS:LSM, LSM-P3 & LSM-TT-B
when installed and used in accordance with the instruction manual provided is in conformity with
the following standards:
BS EN 60204-1:2006, BS 61000-6-1:2001, BS 61000-6-3:2001
following provisions of EEC Directives:
Electro Magnetic Compatability Directive 89/336/EEC with amendments 92/31/EEC.
AGM House, London Rd, Copford, Colchester, Essex CO6 1GT UK
Aquatech-Pressmain Limited Instruction manual\Liquid Level Switch LSM

EC Declaration of Conformity

Low Voltage Directive 73/23/EEC and 93/68/EEC,
I.D.Taylor, I.Eng.MIET. Director, AquaTech-Pressmain Limited.
AquaTech-Pressmain Limited
Telephone: 01206 215121 Fax: 01206 215131
Switch ON: (pushed to the right)
Relay 1 energised when probes E and B
are dry.
Relay 1 releases after timer has expired.
(delay off)
Set switch 3 to ON to use 3 probes (E, A
& B) without timer function.
Audible alarm (optional extra) sounds
when relay 2 operates.
Relay 2 (where fitted) energised when
probes E and D are dry.
Relay 2 (where fitted) releases after timer
has expired. (delay off)
Set switch 7 to ON to use 3 probes (E, C
& D) without timer function.
High sensitivity for fluids with low
conductivity (purer water).
12.11.04
Level Switch LSM
12