Note to this manual
General Safety
Instructions
Protronic
Z-6.510-2428
VDS
Ignition Protection Type
© DICTATOR Technik GmbH • Gutenbergstr. 9 • 86356 Neusäß • Germany
Tel. +49(0)821-24673-0 • Fax +49(0)821-24673-90 • E-mail [email protected] • 20220325
1) General Safety Instructions
Since the RZ-24 central is used in both non-EX hold-open systems
and EX hold-open systems, this manual contains important
information on both areas of application. Information relevant
only for the EX area is marked with
The RZ-24 central is a power supply with integrated tripping device for
hold-open systems on fire doors, smoke evacuation flaps etc.
The RZ-24 is also the central of the DICTATOR hold-open system in
hazardous areas. The central itself is not protected against explosion and
therefore has to be mounted outside the hazardous area.
When installing the ex-proof hold-open system, it is imperative to observe
the instructions for implementing the 2014/34/EU directive and the safety
instructions. Furthermore the regulations, especially regarding the marking,
execution, approval, operation and maintenance, corresponding to the
type approval Z-6.500-2443 of 17 October 19 have to be met.
Only trained professionals may effect the installation; e.g. only a qualified
electrical technician may connect the power supply to the mains. To the
electrical installation following the power supply ( safety extra-low voltage
24 VDC) apply the acknowledged technical regulations for electrical
installations. In the hazardous area all the demands applying to this area
have to be adhered to (type of cables, marking of cables for intrinsical
electric circuits, equipotential bonding etc.).
Only a professional trained by DICTATOR with an approval authorisation
may approve the system.
The relevant regulations must be observed for all work.
The operation of all components is only permitted in undamaged
The accident prevention regulations have to be respected.
The operating company has to determine and document the hazardous
zones according to the explosion protection document where the ex-proof
hold-open system shall be installed.
During installation the respective ignition protection type of every individual
component has to be respected.
The RZ-24 central and the Zener barrier may solely be
installed outside the hazardous area. Only exception is
when they are supplied in a pressure capsulated, ex-proof
housing.
Technical Manual
.
condition.
RZ-24 Central
Page 07.021.03
Page 07.021.3