Dictator RZ-24 Technisches Handbuch - Seite 4

Blättern Sie online oder laden Sie pdf Technisches Handbuch für Stromversorgung Dictator RZ-24 herunter. Dictator RZ-24 19 Seiten. Central

Technical Manual
RZ-24 Central
Ignition Protection Type
- cont.
Installation, Connection
Instructions for Wiring
Repairs
Page 07.021.4
Page 07.021.04
General Safety Instructions - cont.
None of the used components may be modified without written consent
of the manufacturer. This applies in particular to the connection cables
of the magnets. If, for example, the connection cables are shortened,
consultation with our technical customer service department is mandatory
in advance.
When connecting the components of the ex-proof hold-open system,
besides the generally accepted codes of practice you must respect in
particular the on-site requirements, the Equipment and Product
Safety Act, the Ordinance on Hazardous Substances, the Law
on operational safety and other relevant prescriptions for
installations in hazardous areas.
Outside the hazardous area you can use the usual method for connection.
However, inside the hazardous area you may only use certificated
material, e.g. EEx-e terminals and EEx-e terminal boxes. When using
approved electromagnets with IP 65 terminal, please contact our technical
customer service department.
The connection cables have to be installed in such a way that they cannot
be moved and are sufficiently protected against damage. Also here you
strictly have to adhere to the requirements of the respective operating
company. All components of the system, the cables and their connections
have to be clearly marked by the installation contractor.
If nothing else is required on site or by special regulations, the following
specifications have to be respected:
- All works on current circuits may only be effected in the de-
energized state.
- Current circuits of the ignition protection type "m"
(electromagnets): Here it is imperative to respect the demands for
the correct connection of the electromagnets (e.g. every magnet has
to be fused individually, the fuse being upstream of the magnet). Apart
from that apply the requirements of a "normal" installation.
- Current circuits of the ignition protection type "i" (intrinsic
safety) (smoke detectors): Intrinsically safe current circuits have
spatially to be separated from not intrinsically safe ones (separate
laying of cables!). Intrinsically safe current circuits have to marked as
such. When using colour for marking, the cables have to be light blue.
The marking should also include the cable ducts, possible connection
boxes etc.
- Equipotential bonding conductor: The cable (yellow/green) has
to have a cross section of 4 mm
All defect ex-proof components MUST be sent to the factory for repair. An
exchange of the components is possible, an on-site repair unfortunately
not. If the damage of one or more components of an installation might
cause un unsafe state, the complete system has to be shut down until it
has been repaired and is safe again.