Alpha Outback Energy Tetrex 500 Benutzerhandbuch - Seite 4

Blättern Sie online oder laden Sie pdf Benutzerhandbuch für UPS Alpha Outback Energy Tetrex 500 herunter. Alpha Outback Energy Tetrex 500 9 Seiten.

Using the On/Off Button (Continued)
Shut off:
Press the on/off button for more than 3 seconds.
Self test:
When the unit is connected to line power, press the on/off button.
Buzzer off:
Except for the low battery and overload alarms, turn off the buzzer by pressing the on/off button for 1 second.

Alarms and Troubleshooting

This unit has several audible alarms. To turn off the alarm, press the power button.
Slow Alarm (1 beep every 2 seconds):
Low Battery Alarm (1 beep every
discharged. This alarm cannot be shut off.
Overload (continuous beeping):
and restart the unit. This alarm cannot be shut off.
Symptom
Unit does not turn on, the
LED is not on.
Unit is always in battery
mode.
Backup time less than
predicted
The buzzer is continuously
beeping
Most alarms except for low battery and overload. See the troubleshooting table.
1 /2
second):
The unit is operating on battery power and the battery is almost
The unit is overloaded and it automatically turns itself off. Disconnect unnecessary loads
Troubleshooting Table
Causes
The power switch is not
pushed.
Battery voltage less than 20
VDC.
Load less than 20W when
unit is in battery mode.
PCB failure.
Power cord loose.
AC fuse blown or breaker
tripped.
PCB failure.
Battery is not charged.
PCB failure.
The unit is overloaded.
Action
Push it for more than 1 second
Plug the unit into the line for at
least 6 hours to recharge the
battery then restart.
This is normal. The unit's "green
mode" is active.
Contact AOE.
Plug it in.
Replace the fuse or reset the
breaker.
Contact AOE.
Plug the unit into the line for at
least 6 hours to recharge the
battery then restart.
Contact AOE.
Turn off some of the loads.
Page 3 to 7