Blättern Sie online oder laden Sie pdf Erste Schritte für Industrielle Ausrüstung Siemens Simatic S7-400 herunter. Siemens Simatic S7-400 36 Seiten. Block library motor starter sirius for simatic pcs 7 sirius motor starter pcs 7 library v7.1+sp2 / sirius motor starter pcs 7 library v8 migration 8.0+sp1
Auch für Siemens Simatic S7-400: Handbuch (35 seiten), Handbuch (18 seiten)
Procedure for device configuration with GSD file
Table 2- 3
Steps for configuring following a Y-link/redundant H station
Step
Action
1
Select the SIMATIC 400 station in the component view.
•
Select the "Edit > Open Object" menu command.
•
The HW Config opens.
2
If the hardware catalog is not visible, select the "View > Catalog" menu command.
•
Install the necessary GSD file for the motor starter:
•
Menu command "Options > Install GSD file".
In the standard hardware catalog, open the "PROFIBUS DP > Additional Field Devices > I/O > ET 200S > ET
•
200S HighFeature" folder.
Open the folders "Additional Field Devices > I/O > ET 200S > ET 200S High Feature" one after the other
•
Use a drag-and-drop operation to move the ET 200S station and all required modules, such as power
•
modules and motor starters, to the "DP master system". The "Properties" dialog box opens.
Enter the PROFIBUS address.
•
This is the same address as the address of the device station of the motor starter.
Click "OK".
•
The settings are accepted.
3
Compile the hardware configuration: "Station > Save and Compile".
•
Set the PG/PC interface to CP 5613 A2 (PROFIBUS)
•
Download the automation station configuration: "PLC Download".
•
SIRIUS Motor Starter PCS 7 Library "V7.1+SP2"/ "V8 Migration V8.0+SP1"
Getting Started, 08/2013, A5E02897539020A/RS-AA/005