Siemens Simatic S7-400 시작하기 - 페이지 17

{카테고리_이름} Siemens Simatic S7-400에 대한 시작하기을 온라인으로 검색하거나 PDF를 다운로드하세요. Siemens Simatic S7-400 36 페이지. Block library motor starter sirius for simatic pcs 7 sirius motor starter pcs 7 library v7.1+sp2 / sirius motor starter pcs 7 library v8 migration 8.0+sp1
Siemens Simatic S7-400에 대해서도 마찬가지입니다: 매뉴얼 (35 페이지), 매뉴얼 (18 페이지)

Siemens Simatic S7-400 시작하기
Procedure for device configuration with GSD file
Table 2- 3
Steps for configuring following a Y-link/redundant H station
Step
Action
1
Select the SIMATIC 400 station in the component view.
Select the "Edit > Open Object" menu command.
The HW Config opens.
2
If the hardware catalog is not visible, select the "View > Catalog" menu command.
Install the necessary GSD file for the motor starter:
Menu command "Options > Install GSD file".
In the standard hardware catalog, open the "PROFIBUS DP > Additional Field Devices > I/O > ET 200S > ET
200S HighFeature" folder.
Open the folders "Additional Field Devices > I/O > ET 200S > ET 200S High Feature" one after the other
Use a drag-and-drop operation to move the ET 200S station and all required modules, such as power
modules and motor starters, to the "DP master system". The "Properties" dialog box opens.
Enter the PROFIBUS address.
This is the same address as the address of the device station of the motor starter.
Click "OK".
The settings are accepted.
3
Compile the hardware configuration: "Station > Save and Compile".
Set the PG/PC interface to CP 5613 A2 (PROFIBUS)
Download the automation station configuration: "PLC Download".
SIRIUS Motor Starter PCS 7 Library "V7.1+SP2"/ "V8 Migration V8.0+SP1"
Getting Started, 08/2013, A5E02897539020A/RS-AA/005
First steps for the project
2.2 Configuring the device hardware
17