Siemens SIPROTEC T103 Handbuch - Seite 17

Blättern Sie online oder laden Sie pdf Handbuch für Industrielle Ausrüstung Siemens SIPROTEC T103 herunter. Siemens SIPROTEC T103 38 Seiten.

Siemens SIPROTEC T103 Handbuch
2.3.3.5

Fault Indications In Monitor Direction

INF
Semantics
<64>
Start /pick-up L
<65>
Start /pick-up L
<66>
Start /pick-up L
<67>
Start /pick-up N
<68>
General trip
<69>
Trip L
1
<70>
Trip L
2
<71>
Trip L
3
<72>
Trip I>> (back-up operation)
<73>
Fault location X in ohms
<74>
Fault forward/line
<75>
Fault reverse/busbar
<76>
Teleprotection signal transmitted
<77>
Teleprotection signal received
<78>
Zone 1
<79>
Zone 2
<80>
Zone 3
<81>
Zone 4
<82>
Zone 5
<83>
Zone 6
<84>
General start/pick-up
<85>
Breaker failure
<86>
Trip measuring system L
<87>
Trip measuring system L
<88>
Trip measuring system L
<89>
Trip measuring system E
<90>
Trip I>
<91>
Trip I>>
<92>
Trip IN>
<93>
Trip IN>>
2.3.3.6

Auto-reclosure Indications In Monitor Direction

INF
Semantics
<128> CB 'on' by AR
<129> CB 'on' by long-time AR
<130> AR blocked
2.3.3.7

Measurands In Monitor Direction

INF
Semantics
<144> Measurand I
<145> Measurands I, V
<146> Measurands I, V, P, Q
<147> Measurands I
<148> Measurands I
7VU68x Redundant T103 Bus mapping
C53000-L2540-C558-1
1
2
3
1
2
3
, V
N
EN
, V
, P, Q, f
L1,2,3
L1,2,3
IEC 60870-5-103 Interoperability
17