2.3.3.5

Fault Indications In Monitor Direction

INF
Semantics
<64>
Start /pick-up L
<65>
Start /pick-up L
<66>
Start /pick-up L
<67>
Start /pick-up N
<68>
General trip
<69>
Trip L
1
<70>
Trip L
2
<71>
Trip L
3
<72>
Trip I>> (back-up operation)
<73>
Fault location X in ohms
<74>
Fault forward/line
<75>
Fault reverse/busbar
<76>
Teleprotection signal transmitted
<77>
Teleprotection signal received
<78>
Zone 1
<79>
Zone 2
<80>
Zone 3
<81>
Zone 4
<82>
Zone 5
<83>
Zone 6
<84>
General start/pick-up
<85>
Breaker failure
<86>
Trip measuring system L
<87>
Trip measuring system L
<88>
Trip measuring system L
<89>
Trip measuring system E
<90>
Trip I>
<91>
Trip I>>
<92>
Trip IN>
<93>
Trip IN>>
2.3.3.6

Auto-reclosure Indications In Monitor Direction

INF
Semantics
<128> CB 'on' by AR
<129> CB 'on' by long-time AR
<130> AR blocked
2.3.3.7

Measurands In Monitor Direction

INF
Semantics
<144> Measurand I
<145> Measurands I, V
<146> Measurands I, V, P, Q
<147> Measurands I
<148> Measurands I
7VU68x Redundant T103 Bus mapping
C53000-L2540-C558-1
1
2
3
1
2
3
, V
N
EN
, V
, P, Q, f
L1,2,3
L1,2,3
IEC 60870-5-103 Interoperability
17