Siemens ZIC-4A Installationsanleitung Handbuch - Seite 5
Blättern Sie online oder laden Sie pdf Installationsanleitung Handbuch für Kontrolleinheit Siemens ZIC-4A herunter. Siemens ZIC-4A 24 Seiten. Zone indicating card
PRE-INSTALLATION
Siemens Industry, Inc.
Building Technologies Division
TROUBLE
ZONE 3 ACTIVE
TROUBLE
ZONE 4 ACTIVE
TROUBLE
Three rotary dial switches at the bottom of the front panel are used to set the HNET
network address of the ZIC-4A.
The following components must be set prior to inserting the card to the CC-5 (refer
to Figure 2):
S1 Primary Bell Follower Select Switch:
This switch selects Zone 1 as the Primary
Bell Follower. Toggle the S1 switch
towards the bottom of the board if Zone
1 is configured as a Primary Bell Follower;
otherwise toggle it to the top of the
board for normal operation (as shown in
Figure 2.)
S2, Leased Line Select Switches: These
switches select the zones configured for
Leased Line application. Toggle each
switch to the ON position if the corre-
sponding zone is configured as Leased
Line. If the zone is not configured as a
Leased Line application, the correspond-
ing zone switch must be set to the OFF
position.
During card failure, Zone 1 and Zone 2
outputs will activate if the FireFinder-
XLS/Desigo Fire Safety Modular/Cerberus
PRO Modular Alarm bus is asserted,
Zone 3 outputs will activate the if the
FireFinder-XLS/Desigo Fire Safety
Modular/Cerberus PRO Modular Trouble
Bus is asserted. You must configure each
zone to the proper Leased Line remote
monitoring circuit.
Silver line on S1 and jumpers P1 and
P4 indicates normal operation.
(Yellow)
Normally OFF . When illuminated, indi-
cates that the ZIC-4A has detected a
trouble on Zone 2 (open circuit or short
circuit).
(Red)
Normally OFF . When illuminated, indi-
cates that Zone 3 is active.
(Yellow)
Normally OFF . When illuminated, indi-
cates that the ZIC-4A has detected a
trouble on Zone 3 (open circuit or short
circuit).
(Red)
Normally OFF . When illuminated, indi-
cates that Zone 4 is active.
(Yellow)
Normally OFF . When illuminated, indi-
cates that the ZIC-4A has detected a
trouble on Zone 4 (open circuit or short
circuit).
S3
RESET
SWITCH
1
2
3
4
S7
NETWORK
S6
ADDRESS
S4
Figure 2
ZIC-4A Switch Location
5
S2
LEASED LINE
SELECT
EXT
96 PIN DIN
S5
POWER
PLUG CONNECTOR
On
INPUT
POWER
SELECT
BP
POWER
P4
6
5
4
3
2
1
P3
6
5
4
3
2
1
ZONE INPUT
P2
SUPR ENABLE
6
5
4
3
2
1
P1
S1
6
5
4
3
2
1
P/N 315-033050-15