Note to installation of MGW-KNXCS:
1. One KNX module can only connect with one indoor unit;The KNX module should
connect to indoor D1D2E ports.
2. Circuit of MGW-KNXCS is low voltage circuit. Never connect it with a standard
220V/380V circuit or put it into a same Wiring Tube with the circuit.
3. Do not attempt to extend the shield cable by cutting, if it is necessary, use
Terminal Connection Block to connect.
4. After finishing connection, do not use Megger to have the insulation check to the
signal wire.
5. The default physical address of the MGW-KNXCS is 15.15.255,If there are two or
more KNX modules, then the physical addresses can not repeat.The physical
address can be changed by ETS software.
6. Before installation,need prepare KNX power module .
4