Actulux SVM EI 24V-5A Installationsanweisung - Seite 7
Blättern Sie online oder laden Sie pdf Installationsanweisung für Bedienfeld Actulux SVM EI 24V-5A herunter. Actulux SVM EI 24V-5A 13 Seiten. Control panel for fire ventilation
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
LEDs on main board and front panel
LED/colour
Symbol
Operation possibilities for:
LD1/red
Actuator open (red). Lights when actuator opens
LD2/green
Actuator close (green). Lights when actuator closes
LD3/red
Weather sensor active (red). Lights when weather sensor is active
LD4/red
Line error on actuator (red). Lights when actuator has open circuit,
flashes at earth fail or when short circuit occur.
It is not possible to RESET or close with actuator output (see page 7)
LD5/red
Line error on fire switch (red). Lights when fire switch has line error,
flashes when Fireman's Priority Switch has line error
LD6/red
Line error on smoke detector (red). Lights when smoke detector has
line error, flashes at temperatures above 75 °C
LD7/red
Bus error (red). Lights when BUS signal from other controls is
missing. Only relevant if J4-J7 is mounted.
Green
lights if everything is ok
Board + Front
switched off by local error on this control
flashes by error message from other controls received by bus
Yellow
Fault
Board + Front
lights by local error on this control
or by error message from other controls received by bus
*Yellow
Line error
Board + Front
flashes by local error on this control and if the ribbon cable or
jumper is not mounted on J9, or by error message from other
controls received by bus
AC error
*Yellow
Board + Front
flashes by local error on this control
or by error message from other controls received by bus
Alarm
Red
Board + Front
lights red constantly
*Yellow
DC error
Board + Front
flashes at normal speed (1 Hz) by local battery error on this control
or by error message from other controls received by bus
flashes at high speed (10 Hz) by battery voltage below 19V.
Reset by DIP 4: OFF/ON
Blue
Lights blue constantly in open condition (when windows are open)
Board + Front
flashes when actuator is moving up and down
Lights with*
Time for yearly service - please call for supplier (flashes fast)
Fuse specifications
24V
Placement
Fuse value
F1 8A fast ading fuse
1 pcs. for 24V motor output
Alarm/
Comfort
fire
operation
Yes
No
Yes
No
Yes
Only
close
Yes
Only
close
Yes
Only
close
Yes
Yes
Yes
Only
close
Yes
Only
close
Yes
Only
close
Yes
No
Yes
Yes
12
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
Complete jumper settings for SVM EI PCB
Text on board
Factory
Mounted / ON function
mounted
DIP 1
Conf. Fireswitch
No
Fire switch active from 500-3 KΩ.
A short circuit of the smoke detector
input will generate a line error
DIP 2
Failsafe
No
Line error on fire switch or detector
puts the control in alarm
DIP 3
Temp. Detekt
No
Line error on motor line
(upper resistor area) = alarm
DIP 4
Ser
Yes
Active
DIP 5
Snitch
No
LED's "remember" errors (line
errors, AC/Batt. error, bus error). The
LED's can only be switched off/reset
again by setting dip switch off
DIP 6
Fail Relay
No
Failure relay works as indication that
skylight is open
DIP 7
Week open
No
Weekly open (2 sec.) /close
(5 sec.) cycle activated
DIP 8
Option
No
Auto reset (see page 9)
DIP 9
Sprinkler
No
Motor output closes by active
detector (opens by activating the fire
switch)
DIP 10
Bus comfort
No
The control reacts on comfort signal
via bus activity
DIP 11
Bus fire
No
The control reacts on alarm signal
via bus activity
DIP 12
Lock-Out Mode
No
Slaves can enter Lock-Out Mode
see page 18
J1
J1
Yes
Internal Buzzer ON
J3
1 - 2 - 3 - 4
Pos. 1
Connect according to number of
(motor)
27KΩ terminal resistors on actuator
Mot Mon act.
Yes
2 wire line monitoring via 27KΩ
J2
terminal 2-3
(motor)
Ext Li Mon act.
No
3 wire line monitoring with direct
motor connection actuator
J4(Bus)
Start term.
No
First control panel in the bus network
J5(Bus)
+ Master
No
J6(Bus)
Slave
No
Middle and last control panel in the
bus network
J7(Bus)
End term.
No
Last control panel in the bus network
J9
FOIL
Yes in Basic Line monotoring of front cabinet
J11
BatSup->Ø23
No
Battery backup of terminal 23
Others: Reset time = 180 sec. closing // Cut-off motor output and loading after 360 sec. // Comf. var (potetiometer): 1-60 sec.
Dismounted / OFF function
Fire switch active from 0-3 KΩ.
A short circuit of the smoke detector
input will generate alarm
Normal mode
Normal mode
Inactive
Normal mode
Normal mode (works as failure
relay)
Weekly open/close not activated
Normal mode
Normal mode - motor output opens
by ative detectors or fire switches
The control does not react on
comfort signals via bus activity //
NB! Always reaction on weather
signal and failures via bus activity
and own comfort signal
The control does not react on alarm
signal via bus activity
//NB! Always reaction on weather
signal and failures via bus activity
and own alarm signal (detector or
fire switch)
Normal mode
Internal Buzzer OFF
No line monitoring
No line monitoring
See section concerning connection
of controls panels in bus connection,
page 14
Line error flashes
Terminal 23 only AC supplied
13