Actulux SVM EI 24V-5A Installationsanweisung - Seite 9
Blättern Sie online oder laden Sie pdf Installationsanweisung für Bedienfeld Actulux SVM EI 24V-5A herunter. Actulux SVM EI 24V-5A 13 Seiten. Control panel for fire ventilation
LED 2 Actuator closing (green). Lit when actuator is closing.
LED 3 Weather sensor active (red). Lit when weather sensor is active.
LED 4 Line failure actuator (red). Lit for line failure on actuator.
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
LED 5 Line failure fire switch (red). Lit for line failure on fire switch.
LED 6 Line failure smokesensor (red). Lit for line fail. on smokes.
LED 7 BUS failure (red). Lit when local unit is not recieving signal.
Special functions
Sprinkler function:
DIP 9 On - a special function comes in use where sprinkler systems are installed. With this function
activated, the actuator output closes, if smoke-/heat detector input is activated.
If the fire switch is activated, the actuator output opens.
Weekly open/close:
DIP 7 On - the motor output opens shortly (3 seconds) once a week and closes immediately after -
This function is used to give the right tension on the packing of the skylights to keep them watertight.
Function of heat detector in LIP:
DIP 3 On - a heat detector 70-100 °C can be mounted in each LIP. If the temperatur is exceeded, the
control panel goes into alarm and the opening system is opening.
12
LOCKOUT
11
BUS FIRE
Lock-Out Mode:
10
BUS COMFORT
DIP 12 On - see page 18
9
SPRINKLER
8
OPTION
7
WEEK OPEN
6
FAIL RELAY M.
for batteri backup
nal 23
5
SNITCH
4
SERVICE TIMER
1
Fireman's Priority Switch
3
TEMP DETECT
2
The Fireman's Priority switch is an override switch, which makes it possible for the Fireman to control the
FAIL SAFE
1
Con. Fire. Sig
panel regardless of sensor inputs.
Connection/function
DIP settings see page 13
- The CLOSE-switch activates the panel in close condition for 180 seconds, and the panel stays in fire mode.
- The OPEN-switch activates the panel in open condition if not in fire mode, and the panel enters fire mode.
END termination
J7
- The LED output is activated in open condition (windows are open).
BUS Slave
When actuator is moving up or down LED flashes with 1Hz, in case of fail LED flashes with 10 Hz.
J6
- The output is maximum 1 mA 24V.
TART termination
J4
- OPEN and CLOSE switches have line surveillance.
- Only one Fireman's Priority Switch can be connected.
BUS Master
J5
- When activating OPEN and CLOSE at the same time = reset is performed.
- The input is not a part of Configure Fire switch DIP1 = the input is active between 0-3 Kohm.
Connection from
prev. unit.
18
19
20
21
22
23
24
25
26
Comfort
Weather
Prior
Down
ut
®
®
®
®
#111980
Firemans Priority switch
27
CLOSE
OPEN
R
E
S
E
T
1
6
#111980
16
}
See page 12
Cable sizes
It is very important to use the correct cable types and sizes to make sure that the fire ventilation system
meets the standards and works correct in an emergency.
The two most important factors are the ability of the cables to resist heat and to make sure that the
voltage drop in the cables to the actuators do not exceed 15 % at full load on the fire ventilation hatches.
Fire resistant cables according to IEC 60331 must be used for the following functions:
Opening systems with actuators 24V
Fire switch 24V
Smoke detector 24V
Heat detector
Total length of bus cable
* For cable lengths longer than 100m, properly closed shielded cables must be used.
Normal cables can be used for the following functions:
Supply for control 230VAC
Comfort ventilation button 24V
Wind- and rain sensor 24V
Table for SVM EI 24V-5A/8A allowed voltage drop 15% = 3.6V
Power
consumption
per group in
2x1.5 mm²
ampere
2
74 m
4
37 m
6
25 m
8
18 m
Control for Fire and Comfort Ventilation Type SVM EI 24V-5A / SVM EI 24V-8A
2 wires, see diagramme
(3 wires by external line surveillance)
Min. 6 x 0.5 mm² (0.8 mm)
Min. 2 x 0.5 mm² (0.8 mm)
Min. 2 x 0.5 mm² (0.8 mm)
4 x 0.5 mm² (0.8 mm)
e.g. 3 x 1.5 mm² PVIK-J
Min. 3 x 0.5 mm²
Min. 4 x 0.5 mm²
Cable cross section and amount of cores
2x2.5 mm
4x1.5 mm
4x2.5 mm
2x6 mm
²
²
²
(2x1.5+2x1.5)
(2x2.5+2x2.5)
12 3m
148 m
246 m
295 m
61 m
74 m
122 m
148 m
41 m
50 m
82 m
98 m
31 m
36 m
62 m
74 m
17
Max. cable length
100 m*
100 m*
100 m*
300 m*
5x2.5 mm
2x10 mm
²
²
²
(2x2.5+3x2.5)
307 m
492 m
154 m
244 m
102 m
164 m
77 m
124 m