Argina CM+ Installationsanleitung Handbuch - Seite 15

Blättern Sie online oder laden Sie pdf Installationsanleitung Handbuch für Kontrolleinheit Argina CM+ herunter. Argina CM+ 20 Seiten. Conventional fire alarm control panel

Operation without delay (night scheme)
The Delayed Operation LED is extinguished.
In this mode the delay times are NOT active and all alarms will operate immediately.
Switching between day/night
The operating mode of the control panel can be switched using the Day/Night key (operating
level 2).
The yellow LED next to the key shows the status:
- LED off: night scheme: no delay, all alarms operate immediately in the event of an alarm.
- LED on: day scheme: delay times in effect, sirens start after a delay in the event of an alarm.
Adjusting times T1, T2, T3
Select the desired delay time: function 1, 2 or 3 (see
The selected time can now be adjusted using the zone keys. Keys 1 to 9 correspond to 1 to 9
minutes. Key 10 has a value of 0, except for T3, where it means that the alarm devices will not
be switched off automatically.
13.4 Zone set-up: immediate / delayed alarm (Function 4)
Each zone can be set up for immediate or delayed activation. If a zone is set up for no delay, then
delay times T1 and T2 will not be used for that zone, and the alarm devices will be activated
immediately.
Select Function 5 (see
The Installer Code is not entered for this function.
The Fault LEDs show the operational status of each zone: a flashing LED indicates delayed
activation, an extinguished LED indicates activation with no delay.
Each zone's activation can be adjusted using the zone keys.

13.5 Show alarm counter (Function 5)

The alarm counter shows the number of times the control panel has entered the alarm condition.
The alarm counter is not incremented by an alarm in a zone in the test position.
The counter has 3 digits (values 000 to 999) and can only be reset by using the CMPlus.exe
program. Each digit is shown separately by the zone Fault LEDs.
The Fault LEDs for zones 1 to 9 correspond to the values 1 to 9, and the Fault LED for zone 10
represents 0.
Select Function 5 to show the alarm counter.
The Installer Code is not entered for this function.
After the function is selected, the first digit of the counter is shown by the zone's Fault LED; for
example if the zone 10 Fault LED is lit then the first digit is 0.
Press the Zone 2 key to show the second digit; for example if the zone 10 Fault LED is lit then
the second digit is 0.
Press the Zone 3 key to show the third digit; for example if the zone 2 Fault LED is lit then the
third digit is 2.
The digits can easily be shown again by pressing the zone keys again; for example press the
Zone 1 key the show the first digit again.
In this example the fire alarm control panel's alarm counter shows 002.
Selecting the desired
Selecting the desired
function).
function).