Electrical Connections
10. The heater leaves the factory confi gured to operate with two mains supplies, a 24 hour peak supply and an off peak
switched supply (see Fig 10a). The heater can also be operated with a single main supply (Fig. 10b).
Two Mains Supplies
24 hour / peak supply
Off -peak supply
The earth wire should be connected
into the earth terminal block marked E -
Mains Terminal Block
WARNING:
Terminal block Minimum torque of 2Nm and Maximum torque of 2.2Nm
Single Mains Supply
IMPORTANT - This kind of installation relies on the property having a fi xed time period, off -peak energy tariff with 'whole
home switchover' whereby all wiring in the property utilises the off -peak rate when available.
Available fi xed charge times must be manually programmed into the heater to tell it when to charge; no external timers
or contactors are needed. Up-to 4 digital charge times can be set.
Single Supply L = OFF-PEAK L
The brown wire connected to Live - L
The earth wire should be connected
into the earth terminal block marked E -
Mains Terminal Block
NOTE:
The property energy
supplier should be
consulted to confi rm
that the meter and tariff
is suitable for single
supply storage heating
WARNING:
Terminal block Minimum torque of 2Nm and Maximum torque of 2.2Nm
Dual Supply - Storage / Fan circuit (Fig.10A)
Fan Circuit
L = PEAK L
Storage Circuit L = OFF-PEAK L
The brown wire connected to Live - L
Note!
Do not connect to existing off peak wiring, unless the supply to
these circuits is permanently live!
Fan Circuit
N = PEAK N
Storage Circuit N = OFF-PEAK N
The blue wire connected to Neutral - N
Single Supply N = OFF-PEAK N
The blue wire connected to Neutral - N
Rewire the link
wires as shown
in image
Fig. 10a
Fig. 10b