aerauliqa QCmev80 Installationshandbuch - Seite 7
Blättern Sie online oder laden Sie pdf Installationshandbuch für Klimageräte aerauliqa QCmev80 herunter. aerauliqa QCmev80 17 Seiten.
SEN-PIR), which are accessories on request.
Wiring diagram: Fig. 5B - Dip switch configuration: 1000 for QCMEV 80/125 HY (Fig. 5F).
Wiring diagram: Fig. 5B - Dip switch configuration: 1001 for QCMEV 80/125 (Fig. 5F).
Variable speed operation with CTRL-M remote manual controller (accessory on request)
The unit runs at the speed set by turning the knob of the CTRL-M remote manual control
panel (accessory, Fig. 6).
Wiring diagram: Fig. 5C - Dip switch configuration: 0100 for QCMEV 80/125 HY (Fig. 5F).
Wiring diagram: Fig. 5C - Dip switch configuration: 0101 for QCMEV 80/125 (Fig. 5F).
Variable speed operation through external domotic (BMS) system or ballast potentiometer
The unit runs at the speed set by turning the knob of an external 1-10V ballast
potentiometer or set by an external 1-10V signal from a domotic (BMS) system.
Wiring diagram: Fig. 5D - Dip switch configuration: 0110 for QCMEV 80/125 HY (Fig. 5F).
Wiring diagram: Fig. 5D - Dip switch configuration: 0111 for QCMEV 80/125 (Fig. 5F).
Three speed operation with SEL-3V speed selector (accessory on request)
The unit runs at the speed selected by turning the knob of the SEL-3V speed selector
(accessory, Fig. 7).
Speed 1 is set by turning the integral trimmer "V1" in the terminal box.
Speed 2 is set by turning the integral trimmer "V2" in the terminal box.
Speed 3 is the maximum speed achievable by the unit.
Wiring diagram: Fig. 5E - Dip switch configuration: 1000 for QCMEV 80/125 HY (Fig. 5F).
Wiring diagram: Fig. 5E - Dip switch configuration: 1001 for QCMEV 80/125 (Fig. 5F).
For humidistat version only (QCmev 80 HY - QCmev 125 HY)
Whatever is the chosen operation and the speed setting, when the humidity threshold is
reached, the fan speed is increased by 15%.
When the humidity level returns below the threshold, the fan continues to run at increased
speed for a pre-set period of time.
Humidity threshold is adjustable from 50% to 95% via trimmer HY (Fig. 5G).
To deactivate the humidistat function, turn the trimmer HY completely clockwise (position
G).
NOTE: Dip switch number 4 should always be in "0" position for HY unit to enable
humidistat function.
MAINTENANCE
Make sure the mains supply of the unit is disconnected before performing any
maintenance.
The maintenance must be carried out by a qualified technician and in accordance with
local rules and regulations.
STANdARd CONFORMITY
2014/35/EU Low Voltage Directive (LVD)
2014/30/EU Electromagnetic Compatibility (EMC),
in conformity with the following standards:
Electrical Safety: EN60335-1(2012)+A11+A13; EN 60335-2-80(2003)+A1+A2
Electromagnetic Compatibility: EN 55014-1(2017); EN 55014-2(2015); EN 61000-3-
2(2014); EN 61000-3-3(2013).
7