Maintenance Operation and Replacement
of Steam Trap Fitted on the TVS 6000UD
In case the steam trap must be replaced for any reason, please apply the safety procedure as follows:
Closing Procedure
BURN HAZARD!
Close A-A', G-G'
Open B, H, F, D
• After pressure has been relieved, remove bolts and the trap
• Clean the connector block sealing surfaces
• Apply "Never seize" to the new trap bolts (2), insert bolts through connector block making sure the trap is properly positioned
(per ex: inverted bucket in the vertical position). Tighten bolts evenly with a torque of 55-80 N-m
• Resume normal (steam) operation. Please apply the safety procedure as follows:
Opening Procedure
• Close B, D
• Open A-A'
• Check that the steam trap is working properly
• Close F, H
- Check for leaks around the connector block
Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit armstronginternational.com for up-to-date information.
Use caution as burns could occur to personnel.