- ページ 5

コントロールユニット Armstrong TVS 6000UDのPDF インストレーション&オペレーションマニュアルをオンラインで閲覧またはダウンロードできます。Armstrong TVS 6000UD 8 ページ。 Double trap isolation & bleed valve station

Armstrong TVS 6000UD インストレーション&オペレーションマニュアル
Maintenance Operation and Replacement
of Steam Trap Fitted on the TVS 6000UD
In case the steam trap must be replaced for any reason, please apply the safety procedure as follows:

Closing Procedure

BURN HAZARD!
Close A-A', G-G'
Open B, H, F, D
• After pressure has been relieved, remove bolts and the trap
• Clean the connector block sealing surfaces
• Apply "Never seize" to the new trap bolts (2), insert bolts through connector block making sure the trap is properly positioned
(per ex: inverted bucket in the vertical position). Tighten bolts evenly with a torque of 55-80 N-m
• Resume normal (steam) operation. Please apply the safety procedure as follows:

Opening Procedure

• Close B, D
• Open A-A'
• Check that the steam trap is working properly
• Close F, H
- Check for leaks around the connector block
Designs, materials, weights and performance ratings are approximate and subject to change without notice. Visit armstronginternational.com for up-to-date information.
Use caution as burns could occur to personnel.
North America • Latin America • India • Europe / Middle East / Africa • China • Pacific Rim
armstronginternational.com
5