Acorn Safety S0406-CH12 Anweisungen für Installation, Betrieb und Wartung - Seite 3

Blättern Sie online oder laden Sie pdf Anweisungen für Installation, Betrieb und Wartung für Sanitärprodukt Acorn Safety S0406-CH12 herunter. Acorn Safety S0406-CH12 5 Seiten. Drench hoses

Installation & Operation Manual

INSTALLATION INSTRUCTIONS:

Supplies required: (not provided by Acorn)
1. Wall fasteners, washers, anchors and screws.
2. Pipe sealant or Teflon tape for sealing water
connections.
IMPORTANT: FLUSH WATER SUPPLY LINES
PRIOR TO CONNECTION TO SAFETY
EQUIPMENT.
Notes:
Use hand tools and wrenches in a manner which
will prevent marring finished surfaces. Strap
wrenches or tools with plastic jaw linings are
highly recommended.
Refer to Rough-in for location of supply and drain
lines.
Fragments of Teflon tape or pipe sealant residue
can interfere with the proper operation of this unit.
Ensure pipe sealant methods do not cause
contamination in the system.
STEP ONE: WALL MOUNTING
1. Determine desired mounting location and mark
wall using hanger mounting holes.
2 .Install appropriate anchors to receive mounting
screws or bolts (supplied by others).
3. Re-position hanger over anchors and install
mounting screws to fasten hanger securely to
wall.
4. Hang drench hose on hanger.
STEP TWO: SUPPLY LINE
1. Install water line (supplied by others) in close
proximity to drench hose location.
2. Connect 3/8" NPT reinforced hose (supplied with
drench hose) to plumbed water supply.
3. Open water supply.
4. Test for leaks, proper operation and flow.
STEP THREE: SIGNAGE & INSPECTION
1. Position sign with clear visibility, in close proximity
to safety equipment and mark mounting hole
locations.
2. Select appropriate ¼" anchors, screws and
washers (Supplied by others) to install signage.
3. Attach inspection tag supplied, with plastic zip tie.
Acorn Safety
a division of Acorn Engineering
Manual #7109-504-001
MOUNTING
HARDWARE
(PROVIDED BY
INSTALLER)
MOUNTING
HARDWARE
(PROVIDED BY
INSTALLER)
Company
Page 4 of 5
3/8" NPT FITTING
CONNECT TO
WATER LINE
(SUPPLIED BY
INSTALLER)
Revised: 03/22/13