INSTALLATION INSTRUCTIONS:
Supplies required: (not provided by Acorn)
1. Wall fasteners, washers, anchors and screws.
2. Pipe sealant or Teflon tape for sealing water
connections.
IMPORTANT: FLUSH WATER SUPPLY LINES
PRIOR TO CONNECTION TO SAFETY
EQUIPMENT.
Notes:
—
Use hand tools and wrenches in a manner which
will prevent marring finished surfaces. Strap
wrenches or tools with plastic jaw linings are
highly recommended.
—
Refer to Rough-in for location of supply and drain
lines.
—
Fragments of Teflon tape or pipe sealant residue
can interfere with the proper operation of this unit.
Ensure pipe sealant methods do not cause
contamination in the system.
STEP ONE: WALL MOUNTING
1. Determine desired mounting location and mark
wall using hanger mounting holes.
2 .Install appropriate anchors to receive mounting
screws or bolts (supplied by others).
3. Re-position hanger over anchors and install
mounting screws to fasten hanger securely to
wall.
4. Hang drench hose on hanger.
STEP TWO: SUPPLY LINE
1. Install water line (supplied by others) in close
proximity to drench hose location.
2. Connect 3/8" NPT reinforced hose (supplied with
drench hose) to plumbed water supply.
3. Open water supply.
4. Test for leaks, proper operation and flow.
STEP THREE: SIGNAGE & INSPECTION
1. Position sign with clear visibility, in close proximity
to safety equipment and mark mounting hole
locations.
2. Select appropriate ¼" anchors, screws and
washers (Supplied by others) to install signage.
3. Attach inspection tag supplied, with plastic zip tie.
Acorn Safety
a division of Acorn Engineering
Manual #7109-504-001
MOUNTING
HARDWARE
(PROVIDED BY
INSTALLER)
MOUNTING
HARDWARE
(PROVIDED BY
INSTALLER)
Company
™
Page 4 of 5
3/8" NPT FITTING
CONNECT TO
WATER LINE
(SUPPLIED BY
INSTALLER)
Revised: 03/22/13