Distech Controls Allure EC-Smart-Comfort-SF-Dl Installationshandbuch - Seite 6
Blättern Sie online oder laden Sie pdf Installationshandbuch für Kontrollsysteme Distech Controls Allure EC-Smart-Comfort-SF-Dl herunter. Distech Controls Allure EC-Smart-Comfort-SF-Dl 13 Seiten.
Wiring the Allure EC-Smart-Comfort with a Digital Input Cable
The following models feature a digital input cable:
£
Allure EC-Smart-Comfort-S-DI
£
Allure EC-Smart-Comfort-SO-DI
£
Allure EC-Smart-Comfort-SF-DI
£
Allure EC-Smart-Comfort-SOF-DI
The digital input cable is provided unplugged, and it is to be connected into the sensor when mounting the device (see section
Instructions
[pg. 4]).
Each Smart-Light/Blind Series add-on module connected to an Allure EC-Smart-Comfort sensor uses the first two digital inputs available,
starting from DigitalInput1. Therefore, these inputs cannot be used with digital input wires.
For example, if two Smart-Light/Blind Series add-on modules are connected, the first four digital inputs cannot be used. The wiring of the
digital inputs should thus start with DigitalInput5 (blue wire). See the figure below.
Connection of the digital wires to the digital input cable
1. Remove the sleeve from the wires.
2. Remove the protective sheath from each wire to be connected (wires are pre-stripped).
3. Connect the wires to the switches as shown below.
Wire
Digital Input 1
Digital Input 2
Digital Input 3
Digital Input 4
Digital Input 5
Digital Input 6
Digital Input 7
Digital Input 8
Ground wires
All ground wires (black wires) are connected to a common ground.
Therefore, you can use one ground wire dedicated to each digital input, one ground wire for all digital inputs, or a mix of both solutions.
6 / 13
Color
red solid
red/green stripe
yellow solid
yellow/purple stripe
blue solid
blue/grey stripe
white solid
white/brown stripe
black solid
EC- gfx Program input
DigitalInput1
DigitalInput2
DigitalInput3
DigitalInput4
DigitalInput5
DigitalInput6
DigitalInput7
DigitalInput8
none
Mounting