Distech Controls Allure EC-Smart-Comfort-SF-Dl Installationshandbuch - Seite 8

Blättern Sie online oder laden Sie pdf Installationshandbuch für Kontrollsysteme Distech Controls Allure EC-Smart-Comfort-SF-Dl herunter. Distech Controls Allure EC-Smart-Comfort-SF-Dl 13 Seiten.

Supported Quantity
The Allure EC-Smart-Comfort sensor connects to the controller's Subnet Port. Other devices may also be connected to this port in a daisy-chained fash-
ion (see the controller's datasheet for compatibility information and supported quantities).
Each controller supports a specific maximum number of Allure EC-Smart-Comfort sensors. The Subnet ID of all Allure EC-Smart-Comfort sensors must
be set within the indicated addressing range.
The Allure EC-Smart-Comfort Series and Allure EC-Smart-Air Series sensors share the same Subnet ID range: the same address
CANNOT be concurrently assigned to an Allure EC-Smart-Comfort Series sensor AND to an Allure EC-Smart-Air Series sensor.
Controller Model
ECB-PTU Series
ECB-VAV
ECL-PTU Series
ECL-VAV
ECB-VAV-N
ECB-VAVS
ECB-103
ECB-203 Series
ECL-VAV-N
ECL-VAVS
ECL-103
ECL-203 Series
ECB-300
ECB-400
ECB-600
ECL-300
ECL-400
ECL-600
ECY-APEX
ECY-S1000 Series
ECY-VAV series
ECY-303
ECY-PTU
Table 1: Maximum Number of Room Devices by Controller Model, and Allowed Addressing Range
For VAV controller model permitted quantities, see the VAV-Smart Room Control Device Calculator spreadsheet available from the Distech Controls'
Documentation and Resources Portal.
1.
A controller can support a maximum of two (2) Allure series sensor models equipped with a CO
2.
These models support a recommended maximum of four (4) sensors (Allure series sensors and EC-Multi-Sensor series) combined in total. Each Allure series sensor model equipped with a CO
sensor counts as two (2) sensors. For example, if you connect two (2) Allure Series sensor models with CO
connected, then only up to two (2) more Allure series sensor models WITHOUT CO
8 / 13
Room Device
Allure EC-Smart-Comfort
Allure EC-Smart-Air
Allure EC-Smart-Vue
EC-Multi-Sensor
Allure EC-Smart-Comfort
Allure EC-Smart-Air
Allure EC-Smart-Vue
EC-Multi-Sensor
Allure EC-Smart-Comfort
Allure EC-Smart-Air
Allure EC-Smart-Vue
EC-Multi-Sensor
Allure EC-Smart-Comfort
Allure EC-Smart-Air
Allure EC-Smart-Vue
EC-Multi-Sensor
Allure EC-Smart-Comfort
Allure EC-Smart-Air
Allure EC-Smart-Vue
EC-Multi-Sensor
Allure EC-Smart-Comfort
Allure EC-Smart-Air
Allure EC-Smart-Vue
EC-Multi-Sensor
Allure EC-Smart-Comfort
Allure EC-Smart-Air
Allure EC-Smart-Vue
EC-Multi-Sensor
Allure EC-Smart-Comfort
Allure EC-Smart-Air
Allure EC-Smart-Vue
EC-Multi-Sensor
may be connected.
2
Permitted Subnet ID Addressing
Range
1 to 4
1 to 4
1 to 4
1 to 4
1 to 4
-
1 to 6
1 to 12
-
1 to 6
1 to 12
1 to 4
1 to 6
1 to 12
1 to 4
1 to 4
1 to 4
1 to 4
1 to 4
1 to 4
1 to 4
1 to 4
1 to 4
1 to 4
sensor. Any remaining connected Allure series sensor models must be without a CO
2
, no other sensors may be equipped. If only one (1) Allure series sensor model with CO
2
Maximum Number of Room De-
vices
1
4
1
4
Not supported
1
6
1
12
Not supported
1
12
4
1
12
4
1,2
4
1,2
4
1,2
4
sensor.
2
2
is
2