6.5 Measured values

Triggering action
Address
Description
Data type #
40209
ACTION
UINT16
40210
ACTDAT
Simulation of output variables
• Writing into the PERCENT1, PERCENT2, OUTPUT1, OUTPUT2 registers interrupts the signal fl ow to the respective
variable and the desired value is specifi ed (However, percent and output value cannot be simulated simultaneously).
The status of the simulation mode can be read in the STATUS2 status register.
• The simulation mode is terminated by writing 0 into the respective bits in the STATUS2 register.
Current measured variables
Address
Description
Data type #
40257
STATUS1
UINT16
40258
STATUS2
UINT16
40259
INPUT1
REAL
40261
INPUT2
REAL
40263
MEAS1
REAL
40265
MEAS2
REAL
40267
LIMIT1
REAL
40269
LIMIT2
REAL
40271
T_JUNCTION1 REAL
40273
T_JUNCTION2 REAL
40275
ELAPSED
UINT32
40277
PERCENT1
REAL
40279
PERCENT2
REAL
40281
OUTPUT1
REAL
40283
OUTPUT2
REAL
10
Default
Description
0
This register starts actions.
Action Description
18
Input 1: With short-circuited input terminals, the line calibration is realised and the measured
parameters are stored in the device.
This procedure is indicated by a fl ashing green LED.
19
Line calibration at Input 2 (same as Input 1)
Additional information for the implementation of an action.
Default
Description
0
Status 1
Bit
Description
0
Reserved
1
Reserved
2
Device fault
3
Parameter fault
4
Sensor breakage
5
Sensor short circuit
6
Reserved
7
Sensor breakage
8
Sensor short circuit
9
Reserved
10
Alarm 1
11
Alarm 2 (relay 1 status before inverting)
12
Limit value 1
13
Limit value 2
14
Relay 1 status
15
Device reset or new parameter values
0
Status of the simulation mode: A set bit indicates the simulation mode of the respective register.
Bit
Description
0
Output 1 (PERCENT1)
1
Output 1 (OUTPUT1)
2
Output 2 (PERCENT2)
3
Output 2 (OUTPUT2)
The simulation mode is terminated by writing zeros into the respective bit positions (0..3).
0.0
Measured value Input 1
0.0
Measured value Input 2
0.0
Measured variable for Output 1
0.0
Measured variable for Output 2
0.0
Measured variable for Limit value 1
0.0
Measured variable for Limit value 2
0.0
Cold junction temperature Input 1
0.0
Cold junction temperature Input 2
0
Operation hour counter [s ]
0.0
Output 1: Scaled output variable in %
0.0
Output 2: Scaled output variable in %
0.0
Output 1 [mA] / [V]
0.0
Output 2 [mA] / [V]
Operating instructions V604s Be
Input 1
Input 1
Input 2
Input 2