Arton ARTON-DL Benutzerhandbuch - Seite 4

Blättern Sie online oder laden Sie pdf Benutzerhandbuch für Rauchmelder Arton ARTON-DL herunter. Arton ARTON-DL 10 Seiten. Linear optical smoke detector
Auch für Arton ARTON-DL: Benutzerhandbuch (7 seiten)

6.1  The  installation  should  be  made  according  to  a  pre‐elaborate  plan  where  the 
requirements of the manual should be considered.   
ATTENTION:  Only  one  detector  should  be  connected  to  a  fire  alarm  loop.  It  is 
recommended  to  make  connections  of  a    control  panel  with  the  transmitter  and  the  
receiver with the transmitter by twisted‐wire cable and lay in the special earthed cable 
channels.  Shielded  cable  should  be  used  to  provide  additional  protection  against 
electrical obstacles.  It is not recommended to place fire alarm system cables in common 
cable channels with other electrical wires.  
6.2  It  is  not  recommended  to  mount  the  units  in  places  where  the  gases,  vapour  
and aerosols can cause corrosion. During repair works additional cover should be used to 
protect units against debris.  
6.3  The  detector's  sensitive  zone  is  the  infrared  beam  between  the  receiver  and 
transmitter. The sensitive zone diameter is determined by the optical system window. The 
sensitive zone should not be overlapped by any objects. 
6.4 The direct light exposure of the optical system window is not allowed.  
6.5 Units of detectors should be installed to a rigid base (main wall, column, rafter 
etc.) in an accessible   place.  
Note:  It  is  allowed  to  install  several  detectors  in  one  room  allocating  sensitive 
zones parallel to each other.  When the distance between parallel optical axes of sensitive 
zones is less than  3 meters,  different detector units should be mounted on the same wall: 
transmitter, receiver, transmitter  and so on. 
6.6 Mark out the transmitter and receiver mounting places according to Figure1. 
6.7 Fix the receiver and transmitter. 
6.8 Connect to a control panel according to Figure 3‐ Figure 5.  
 
7.1 Adjustment 
7.1.1 Loose Rx and Tx bracket attaching screws, direct the optical system windows 
to each other.  
7.1.2  Tighten  screw  joints  with  force  ensuring  the  fixation  of  the  units'  chosen 
position and possibility of the following adjustment.  
7.2 Calibration  
7.2.1  The  RANGE  switch  on  Rx  unit  sets  the  distance  between  Tx  and  Rx.  The 
RANGE switch should be set to the unpressed position if  the distance between the units is 
up to 30 m. When the distance is greater than 30 m ‐  to the unpressed position.   
7.2.2 Set the CALIBRATION switch on Rx to the pressed position.   
7.2.3  Turn  the  fire  alarm  system  on.  The  voltage  drop  on  the  EUI‐1  contacts  «7» 
and  «8»  should  not  be  less  than  8  V.  In  10  sec  after  energizing  both  LEDs  will 
simultaneously flash on Tx every 1 sec. The indicator on EIU‐1.1 shall be continuously lit. 
Depending  on  the  adjustment  precision,  the  following  combinations  of  optical 
indication on Rx are possible:  
‐ bright flashes every 1sec when high level of optical signal has been detected; 
‐ low brightness flashes of the left indicator every 1 sec and right indicator is off 
when normal level of optical signal has been detected; 
‐ bright  flashes  of  the  right  indicator  and  low  brightness  flashes  of  the  left 
indicator every 1 sec when low level of optical signal has been detected; 
6 INSTALLATION 
7 ALIGNMENT AND CHECKING FOR PROPER OPERATION