‐ bright flashes of both indicators every 0.5 sec when adjustment of the receiver 
and transmitter has been made incorrectly 
‐  flashes  at    different  intervals  (0.5  sec  and  2  sec),  and  a  control  panel  will    fix  
open‐circuit  in  alarm  loop  when  the  electric  connection  between  the  receiver  and 
transmitter is absent.  
7.2.4  If  the  optical  signal  level  is  high  it  is  necessary  to  attain  the  normal  signal 
level by slowly turning the calibration regulator counter‐clockwise. It is allowed to change 
the RANGE switch's position if necessary.  
7.2.5 If the optical signal level is normal it is necessary to set the high level of signal 
slowly turning the calibration regulator clockwise  
and  then  to  set  again  the  normal  level  of  signal  slowly  turning  the  calibration 
regulator counter‐clockwise.  
7.2.6 If the optical signal level is  low it is necessary: 
‐  set the normal level of signal turning the sensitivity adjustment screw clockwise; 
‐  set the high level of signal turning the sensitivity adjustment screw clockwise; 
‐  set the normal level of signal turning the sensitivity adjustment screw counter‐
clockwise. 
When the normal or high signal level can not be set with the sensitivity adjustment 
screw,  it  is  necessary  to  check  the  RANGE  switch  position  and  mechanically  adjust  the 
receiver and transmitter again.  
7.2.7  Attain  the  optimal  coaxiality  of  the  optical  system  windows'  axes  of  the 
receiver  and  transmitter,  when  any  their  deviation  in  horizontal  and  vertical  planes  only 
leads  to  optical  signal  level  decrease.  Return  the  unit  to  the  position  corresponding  to 
normal signal level.   
7.2.8  If  any  deviation  of  the  receiver  or  transmitter  leads  to  optical  signal  level 
increase,  it is necessary to fix the unit's position,  to set the normal signal level with the 
calibration regulator. Then repeat the previous action.  
7.2.9 Tighten attachment screws of the receiver and transmitter to brackets. The 
status of the receiver's indicators should not change.  
7.2.10  Calibrate  the  detector  attaining  the  normal  signal  level,  turning  the 
calibration  regulator  counter‐clockwise  and  set  it  to  the  position  near  the  indicators' 
switch from the normal signal level mode to the low one.  
7.3 Verification of fire alarm system
7.3.1 De‐energize the loop for not less than 5 s. After power supply was restored in 
not more than 10 s the detector shall go to the standby mode of operation.  
7.3.2 Obscure infrared beam between the receiver and transmitter with a partition 
which  is    opaque  for  infrared  light.  In  5  sec  after  the  fixation  of  the  partition  the  left 
indicator  of  the  receiver  will  turn  on  for  about  5  sec.  During  this  period  the  current 
consumption  will  increase  by  25±5  mA  which  the  control  panel  will  interpret  as  a  FAULT 
message. If the power of the loop will be off then in 5 sec the detector will automatically 
go to the standby mode. If within the next 10 sec the partition will not be removed out of 
the  sensitive  zone,  the  detector  will  go  to  the  fire  mode.    The  current  consumption  will 
increase  by  8±1,6  mA  in  the  fire  mode,  and  the  left  indicator  shall  pulse  with  low 
brightness and frequency 1±0,1 Hz. 
7.3.3 Remove the partition from the sensitive zone and de‐energize the loop for at 
least 5 sec.