Cutler-Hammer Flex Shaft Schnellstart-Handbuch - Seite 4
Blättern Sie online oder laden Sie pdf Schnellstart-Handbuch für Industrielle Ausrüstung Cutler-Hammer Flex Shaft herunter. Cutler-Hammer Flex Shaft 8 Seiten.
I.L. 15606C
Page 4
Situation:
Breaker resets after tripping, but does not turn ON.
Adjustment:
Loosen the 1/4-28 adjusting nut that is located on the
end of the shaft and turn towards the end of the shaft
about 1/5-2 turns. Re-tighten the adjusting nut that is
closest to the black cap to the handle extension and the
outing adjusting nut. Re-check for the ON, OFF and
RESET position. If not successful, and the adjusting nut
on the end of the shaft is two threads from the end,
loosen the bulk head nuts, and shift the cable towards
the line end of the breaker. Re-tighten the bulk head
nuts. Re-check for the ON, OFF and RESET position. If
not successful, repeat the beginning steps.
If any other adjustment problems should arise, contact
your local Cutler-Hammer representative.
Effective 2/01