All damages/faults must be rectified before proceeding.
Switch ON the Panel. During this period the following LED's have to glow to ensure
system is in healthy condition.
Note: Apart from the above green LED's if any other amber or red LED is ON, it is
indicating respective fire or faults. Rectify the fire or faults before proceeding to
any other operation.

INDICATORS AND CONTROLS

INDICATORS:
SYSTEM ON: In the Normal Condition only SYSTEM ON green LED will be
illuminated. There should be no other amber/red LED visual indication or audible tone.
POWER FAULT: When power fault conditions like mains fail the AC FAIL amber
LED will glow and SYSTEM ON will be off.
BATTERY LOW: When battery voltage goes bellow a certain voltage then BATT LOW
amber LED will glow.
SILENCE: When ever silence switch is pressed to mute internal/external sounder, the
amber color SILENCE LED will glow.
ZONE FAULT: When the fault OPEN/SHORT is occurred in the zone, it will be
identified by zone fault LED and common FAULT LED. The fault zone LED will glow
continuously until the fault is rectified.
Note: During the above fault condition, apart from the specific fault identification LED,
common fault relay and Local buzzer with intermittent tone will be activated.
During this time, if SILENCE is activated, intermittent tone will be silenced.
FIRE: When Fire is detected by the control panel via the Detector/MCP, the
corresponding zone fire red LED will be illuminated along with the common fire red
LED. By the time hooter, potential free contact and local buzzer (continuous tone) will be
activated. If SILENCE is accepted by the panel after the fire, it will mute the external
hooters and internal buzzer. It can be identified by silenced LED ON.
The FIRE LED indication will remain ON condition till the panel is RESET.
AUTO/MANUAL: Green AUTO LED will glow when the panel's all the operations
work in automatic condition. Amber MANUAL LED will glow when panel is in manual
mode.
ASES Security Pvt Ltd
437/2, Main Road, Mandwali Fazalpur, Delhi-110092
A. SYSTEM ON
Page 4