UP/DOWN: These to switches are used to set the delay time for gas discharge. Steps to
set the delay time:
a) Press the UP switch for 5 sec continuously, display will blink once.
b) Now press UP/DOWN to select the delay time.
c) Press DOWN switch for 5sec continuously, display will blink once and the
delay time is saved in memory.
KEY LOCK: This lock is used to enable or disable the control switches at the front of
the panel. When key is in ON condition, all the control switches of the panel is in active
condition. When key is in OFF condition, RESET, LAMPTEST, SILENCE switches will
function in normal condition but DISABLE, ABORT, MANUAL RELEAS,
AUTO/MANUAL switches not be in active condition.
TECHNICAL DATA
Panel Operating Condition Operating Voltage
AC Power
Standby
Operating Temperature
Operating Humidity
Zone Operating Condition
Normal Loop Voltage
Open Threshold Current
Short Threshold Current
Fire Threshold Current
Alarm Outputs Hooter Output : 750mA @24v DC (Normal)
NB: Hooter output current can be increased as per customer requirement.
Remote Outputs
Fire Contact1 (C,NO,NC) : 240v AC@2A /24v DC@ 5A
Fault Contact (C,NO,NC) : 240v AC@2A /24v DC@ 5A
General
Weight
Size
Color
ASES Security Pvt Ltd
437/2, Main Road, Mandwali Fazalpur, Delhi-110092
: 220v AC, 50Hz ± 10%
: 24v DC
: 0°C to 40°C
: 95% (non-condensing)
: 23v DC
: 4.4 mA
: 35 mA
: 15 – 35 mA
: 4 Kgs (without battery)
: 14" x 10" x 4" mm
(width x height x depth)
: Broken white