Ambirad VISION COMPACT VC12 Manual de funcionamiento, mantenimiento y revisión - Página 7

Navegue en línea o descargue pdf Manual de funcionamiento, mantenimiento y revisión para Calentador de gas Ambirad VISION COMPACT VC12. Ambirad VISION COMPACT VC12 19 páginas. Gas fired radiant tube heaters

9 Installation of Vision Compact
heater
Health & safety
A qualified installer is required to install the
appliance in accordance with the rules in
force, and should the need ever arise to
convert the appliance for use with other
Installation
There is no on site assembly required for the
VISION COMPACT of heater.
Attach an appropriate hanging attachment
to each of the four hanging brackets.
The heater can be installed with the
packaging in place to protect the casing
from damage during installation.
Raise the heater into the air and affix to the
chain previously located of 4mm (minimum)
gauge galvanised welded link construction.
Alternatively, 10mm diameter mild steel
drop rods can be used.
Figure 4 Mounting of Vision Compact heater
When chain supports have an angle
of inclination greater than
equal and opposite support is
recommended.
Vertical or inclined suspension
on this plane is acceptable.
Wall mounting brackets must support the
heater at an angle of inclination between
30˚ and 45˚, and are available from the
manufacturer. The angle can be varied by
adjusting the drop rods or chain on each
bracket. The bracket positions are critical
and when suspended they should have the
same orientation i.e. all the same angle.
Note When installing the heater at an angle
the combustion fan outlet should be
positioned so that it remains vertical.
It is recommended that sufficient clearance
from any fixed structure (e.g. a wall) is given
above the burner and behind the burner /
fan compartment to allow sufficient room
for the service of the heater. (See section 8
on clearances).
Note As a part of the heaters annual service
all dust deposits on the top of the reflector
should be removed before the start of each
heating season.
15
° an
*
*
Drop rod with
formed hook.
Shackle method of attachment. Pin must
be tightened by Pipe grips or Pliers.
Important
IMPORTANT
The heater should slope downwards towards the
*
towards the Return bend
These angles to be equal
and not more than 45°
Return Bend by approx. 10mm for both
horizontal and Wall mounted installations.
horizontal and wall mounted installations.
15° max
Vertical suspension chain ideal.
Where supports are inclined max.
recommended angle of inclination
: The Heater should
slope downwards
by approx. 10mm for both
15
°
5