DoorHan PCB-SH380 Manual de inicio rápido - Página 3

Navegue en línea o descargue pdf Manual de inicio rápido para Controlador DoorHan PCB-SH380. DoorHan PCB-SH380 8 páginas. Control board

1.2. CONTROL BOARD TERMINAL BLOCKS
1. Connection of supply voltage (X2 terminal block)
400 V supply voltage connect to terminals «PE», «N»,«L1», «L2», «L3».
NOTE. If, after mounting the operator it moves down when the «UP» button is pressed, the positions of L1 and L2 must
be reversed.
2. Motor (X1 terminal block)
Connect the motor to terminals «W», «V» and «U». 400V motor: max. operating current < 9 A, wattage ≤ 4 kW.
3. Limit switches (X6 terminal block)
Connect the «CL» (closing switch), «OP» (opening switch) limit switches and «GND» (common wire).
4. 3-position control post, key-switch and safety devices (X4, X5 and X6 terminal blocks)
Connect the 3-position control post to the terminals «OPEN», «STOP», «CLOSE» and «GND».
Connect the key-switch to terminals «SBS» and «GND».
Connect the output contacts of the safety devices to the terminals «Ph.CL» and «GND»
WARNING!
If 3-position control post and safety devices are not used, install a jumper between «STOP», «Ph.CL» and «GND».
Voltage: 400V
3~Motor: 400V
Key-switch
3-button control station and safety devices
CONTROL BOARD
3