Akytec MU110-6U Manual del usuario - Página 12
Navegue en línea o descargue pdf Manual del usuario para Sistemas de E/S Akytec MU110-6U. Akytec MU110-6U 18 páginas. Analog output module 6 channel
Restore factory settings
7
Restore factory settings
If the communication between the module and PC cannot be established and the network
parameters of the module are unknown, the default network settings should be restored.
Proceed as follows:
─
power off the module
─
open the front cover
─
set the jumper X2
─
the module will operate with the default network parameters, the user settings
remain stored
─
switch the power on
Dangerous voltage
The voltage on some components of the circuit board can be dangerous! Direct
DANGER
contact with the circuit board or penetration of a foreign body in the enclosure
must be avoided!
─
start the "M110 Configurator" software
─
set the parameters to default (see Table 7.1) or click "Use factory settings" (see
Fig. 7.1) in the dialog window "Connection to device"
─
click "Connect" to establish the connection with factory settings
─
the main window with the device mask opens
─
saved user parameters can be read now (see Fig. 7.2)
─
open the folder "Network parameters" and note the user network parameters
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
Fig. 7.1 "Connection to device" dialog window
Fig. 7.2 Device mask
11