Restore factory settings

7
Restore factory settings
If the communication between the module and PC cannot be established and the network
parameters of the module are unknown, the default network settings should be restored.
Proceed as follows:
power off the module
open the front cover
set the jumper X2
the module will operate with the default network parameters, the user settings
remain stored
switch the power on
Dangerous voltage
The voltage on some components of the circuit board can be dangerous! Direct
DANGER
contact with the circuit board or penetration of a foreign body in the enclosure
must be avoided!
start the "M110 Configurator" software
set the parameters to default (see Table 7.1) or click "Use factory settings" (see
Fig. 7.1) in the dialog window "Connection to device"
click "Connect" to establish the connection with factory settings
the main window with the device mask opens
saved user parameters can be read now (see Fig. 7.2)
open the folder "Network parameters" and note the user network parameters
akYtec GmbH · Vahrenwalder Str. 269 A · 30179 Hannover · Germany Tel.: +49 (0) 511 16 59 672-0 · www.akytec.de
Fig. 7.1 "Connection to device" dialog window
Fig. 7.2 Device mask